Lucent Technologies Model 3000 UPS Operator's Manual (167Ć405Ć119 Issue 3)

57

Troubleshooting

The UPS is designed for durable, automatic operation and also alerts you whenever

potential operating problems may occur. Use the following troubleshooting chart to

determine the UPS alarm condition.

Unlit
Amber
Green
Flashing

Indicator Legend

Condition

Possible Cause

Action

UPS does not turn on.

UPS is not plugged in.

Plug UPS into working outlet.

Dead wall socket.

Test wall socket, repair as required.

UPS input breaker is tripped.

Reduce load, then reset breaker.

Load does not turn on.

UPS has not been activated.

Press the Output

|

On button for one

second, then release.

UPS beeps occasionally.

Normal operation.

None. UPS is protecting your system.

UPS input breaker trips.

Load fault.

Check the load.

Disconnect faulty load equipment.

Wait several minutes before resetting

the UPS input breaker.

Restart the load.

Indicator remains

lit, even though line

l

i

Utility line is out of

specification.

Test wall socket, repair as required.

voltage is present.

UPS input breaker is tripped.

Reduce load, then reset breaker.

UPS does not provide

the expected backup

time

Low battery capacity.

Allow battery to charge for 24 hours,

then retest.

time.

Protected equipment power

requirements exceed UPS

capacity.

Reduce load, then retest.

Communications do not

function properly.

Incorrect communications

cabling.

Verify cable integrity (see page 51).

Incorrect baud rate.

Select a new baud rate (see page 50).

Incorrect communication mode. Select a new communication mode

(see Chapter 5).