Lucent Technologies Uninterruptible Power Systems 3000 VA User Manual

Page 42

Advertising
background image

Installation

3

Lucent Technologies Model 3000 UPS Operator's Manual (167Ć405Ć119 Issue 3)

32

1 Place the conduit through the access hole on the junction box (see

Figure 10). Connect the exposed conduit wires to the corresponding

compression terminals (see the following table). Tighten the compression

terminals with a screwdriver.

2 Pivot the REPO receptacle guard out of the way, plug the REPO

plug/receptacle UPS connector into the REPO receptacle on the UPS rear

panel(see Figure 5 on page 26 or Figure 6 on page 27). Twist the

connector in place.

Mounting Holes

Plug/Receptacle

UPS Connector

Three Foot Cord

Terminal Block

Access Hole

for Conduit

Figure 10. REPO Cord Junction Box

Power Cable Terminations

Tightening Torque

Wire Function

Terminal

Position

Terminal Wire

Size Rating*

Entrelec

Phoenix

Contact

REPO

L1

TB1Ć4

lb/

lb/

L2

TB1Ć5

12Ć22 AWG

(4Ć0 mm

2

)

3.5 - 5.3 lb/in

5.6 - 6.8 lb/in

Ground

TB1Ć6

(

)

*Suggested wire size is #18ĆAWG (0.75 mm

2

) 75_C copper wire minimum.

NOTE: The REPO function activates when L1 and L2 are shorted together.