Ups serial communications menu – Lucent Technologies Uninterruptible Power Systems 3000 VA User Manual

Page 57

Advertising
background image

Communication 5

Lucent Technologies Model 3000 UPS Operator's Manual (167Ć405Ć119 Issue 3)

47

3 Press and hold the Output

Off button a second timeuntil thealarm

beeps again.
A single indicator, corresponding with the current setting, remains

flashing.

4 Press the Output

Off button to scroll through thecommunication

options, top to bottom. Each timeyou press thebutton, theUPS beeps and

the next indicator flashes.

NOTE

If you do not save a selection within two minutes, the setup automatically aborts

and switches back to the original configuration.

5 Press and hold the Output

On button until the alarm beeps to select and

savea communication option. Failureto releasethebutton immediately

after thebeep will causetheUPS to abort thesetup.

6 Press the Output

On button again to return the UPS to Normal Mode.

NOTE

Printer Mode selections are the only serial communication modes available from

the front panel.

UPS Serial Communications Menu

With the UPS Serial Communications (Main) Menu, you can view or select UPS

communication modes, baud rates, and LAN configurations. To change or display

thecurrent communications configuration:

1 Connect the UPS serial port to a video monitor with a serial interface or to

your computer's serial port. If you are using shutdown software, the UPS

should already be connected to your computer.

2 Set your terminal so that it matches the baud rate of the UPS (usually

2400 baud, 8 bits, No parity, 1 stop bit). Refer to your terminal or

operating system documentation for details on configuring your terminal

communication settings.

3 At the terminal prompt, press

Control-C

until theUPS Serial

Communications Menu appears.