For seismic installation, For stability – Lucent Technologies Uninterruptible Power Systems 3000 VA User Manual

Page 35

Advertising
background image

Installation 3

Lucent Technologies Model 3000 UPS Operator's Manual (167Ć405Ć119 Issue 3)

25

2 If you are using the floor mounting plate, complete Steps A and B. This

plate is required only for seismic applications, but can also be used to

prevent rolling or tipping of the assembled rack.

A For Seismic Installation

Prepare the floor by referring to the hole pattern shown below. The

mounting plate has four 0.375 diameter floor mounting holes for

earthquake bolts (not provided). Secure the plate to the floor.

WALL

11.0I minimum

recommended for

cabling

16.16I

Unit

Depth

10.0I

12.5I

Unit

Width

6.5I

3.0I

3.5I

Seismic Mounting

Holes

FRONT

For Stability
The plate does not need to be mounted to the floor, but must be

secured to the caster base to prevent the stack from rolling.

B Secure the caster base to the mounting plate using four of the

1/4Ć20 x 1/2 screws provided. See Figure 3 or Figure 4 for part

locations.

3 Stack the modules onto the caster base according to the stacking order

shown in Figure 3 or Figure 4.
Make sure the first module nests on the base and each additional module

nests on the preceding one.

If multiple Stacking Modules are used, the caster bases may be secured

together on the side with two of the 1/4Ć20 x 1/2 screws provided.