Installation 3

Lucent Technologies Model 3000 UPS Operator's Manual (167Ć405Ć119 Issue 3)

31

22 See the following table for specifications andtightening torque.

Power Cable Terminations

Tightening Torque

Wire Function

Terminal

Position

Terminal Wire

Size Rating*

Entrelec

Phoenix

Contact

Input

Ground

1

22-12 AWG

(0.34-4 mm

2

)

3.5 - 5.3 lb/in

5.6 - 6.8 lb/in

L1

2

lb/

lb/

L2/Neutral

3

18-10 AWG

2

3 5 5 3 lb/in

4 5 7 0 lb/in

Output

L1

5

(0.75-6 mm

2

)

3.5 - 5.3 lb/in

4.5 - 7.0 lb/in

L2/Neutral

6

Ground

8

22-12 AWG

2

3 5 5 3 lb/in

5 6 6 8 lb/in

No Connection

4, 7

(0.34-4 mm

2

)

3.5 - 5.3 lb/in

5.6 - 6.8 lb/in

*Use #16ĆAWG (1.5 mm

2

) 75_C copper wire minimum.

23 Replace the terminal box cover.

24 If you are using a Remote Emergency PowerĆOff (REPO) switch, follow the

instructions in REPO Installation" on page 31.

25 Start the UPS according to the UPS with Bypass Module Startup"

procedure on page 33.

REPO Installation

WARNING

Only qualified service personnel (such as a licensed electrician) should

perform the hardwired installation.

The REPO switch is a customerĆsuppliedswitch that can disconnect UPS output

voltage from your protectedequipment. To use a REPO switch, you needexternal

wiring anda switch with the following specifications:

H The switch shouldbe a wallĆmounted, momentaryĆcontact, normally open,

pushbutton switch.

H Minimum ratings of 240 Vac and35 mA.
H Wire shouldbe 18 AWG minimum.

CAUTION

The black and white REPO wires are at highĆvoltage potential (240V). Refer

to yourlocal electrical code forproperinstallation of the highĆvoltage REPO wires.