Installation

3

Lucent Technologies Model 3000 UPS Operator's Manual (167Ć405Ć119 Issue 3)

28

8 If additional battery modules are to be used, plug the battery cord of the

second module into the external battery connector of the first battery

module. Follow this procedure for each additional battery module or

Extended Battery Cabinet.

9 Remove the breaker tie from the circuit breaker on all battery modules or

EBCs.

10 Turn the circuit breaker on all battery modules to the ON (

|

) position.

11 Two tie wraps are included with the UPS to secure the YĆcord to the input

and output receptacles on the UPS rear panel. Insert the tie wrap through

the slot on each tie wrap mount.

12 Plug the YĆcord of the Bypass Module into the power connectors on the

UPS rear panel as shown in Figure 5 or Figure 6.

13 Verify that the plugs are fully seated. Loop the tie wraps around the YĆcord

connections and tighten to secure the cord to the rear panel.

NOTE

Allow sufficient slack in the cord between the receptacle and the tie wrap. At

least 12I (30 cm) of slack is recommended.

14 If your Bypass Module is a plug/receptacle unit, continue to Step 15. If

your Bypass Module is hardwired, skip to Step 19.

15 If an Extended Power Distribution Module (EPDM) is required, plug the

EPDM into the power output receptacle on the Bypass Module rear panel.

16 The equipment to be protected by the UPS should be powered off. Plug the

equipment into the power output receptacles on the Bypass Module rear

panel.
DO NOT protect laser printers with the UPS because of the exceptionally

high power requirements of the heating elements.

17 If you are using a Remote Emergency PowerĆOff (REPO) switch, follow the

instructions in REPO Installation" on page 31.

18 Start the UPS according to the UPS with Bypass Module Startup"

procedure on page 33.