6.0 System Details

12

© Baxi Heating UK Ltd 2009

6.5

System Filling and Pressurising

1. A filling point connection on the central heating

return pipework must be provided to facilitate initial

filling and pressurising and also any subsequent water

loss replacement/refilling.

2. There are connection points on the mains cold water

inlet and central heating return isolating taps (Fig. 5) to

which the optional filling loop kit (Part No. 248221) can

be assembled.

3. The filling method adopted must be in accordance

with all relevant water supply regulations and use

approved equipment.

4. Your attention is drawn to,

for GB: guidance G24.2 and recommendation R24.2 of

the Water Regulations Guide.

for IE: the current edition of I.S. 813. “Domestic Gas

Installations”.

5. The sealed primary circuits may be filled or

replenished by means of a temporary connection

between the circuit and a supply pipe provided a

‘Listed’ double check valve or some other no less

effective backflow prevention device is permanently

connected at the inlet to the circuit and the temporary

connection is removed after use.

6.6

Expansion Vessel
(Central Heating only)

1. The appliance expansion vessel is pre-charged to 0.5

bar. Therefore, the minimum cold fill pressure is 0.5 bar.

The vessel is suitable for correct operation for system

capacities up to 125 litres. For greater system capacities

an additional expansion vessel must be fitted. For GB

refer to BS 7074 Pt 1. For IE, the current edition of

I.S. 813 “Domestic Gas Installations”.

6.7

Safety Pressure Relief Valve (Fig. 6)

1. The pressure relief valve is set at 3 bar, therefore all

pipework, fittings, etc. should be suitable for pressures in

excess of 3 bar.

2. The pressure relief discharge pipe should be not less

than 15mm dia, run continuously downward, and

discharge outside the building, preferably over a drain. It

should be routed in such a manner that no hazard

occurs to occupants or causes damage to wiring or

electrical components. The end of the pipe should

terminate facing down and towards the wall.

3. The discharge must not be above a window,

entrance or other public access. Consideration must be

given to the possibility that boiling water/steam could

discharge from the pipe.

4. A remote relief valve kit is available to enable the

boiler to be installed in cellars or similar locations below

outside ground level (kit no. 5121379).

Fig. 4

Fig. 6

Stop
Valve

Double
Check
Valve

DHW
Mains
Inlet

CH
Return

Temporary
Hose

Pressure Relief Valve

Discharge Pipe

Stop
Valve

Filling Loop

Fig. 5