Fault Finding

Replace PCB

G

Check and correct if necessary
1. Ignition electrode and lead
2. Electrode connection
3. Spark gap and position

230V at Main PCB - M4
connector across terminals
37 & 38. Check wiring

YES

NO

Replace gas valve

electrical plug/igniter

assy

YES

H

YES

Check the burner setting pressure of the

gas valve

(see Section 11.2 of Commissioning)

1.

Replace gas valve

NO

Replace PCB

2.

Voltage at modulating coil of gas valve is:
Max. burner press.approx 9V DC (13V DC LPG)
Min. burner press.approx 1V DC

Current at modulating coil of gas valve is:
(Use an instrument with average function for this
measure)
30 ÷ 230 mA DC (45 ÷ 310 mA DC LPG)

Check and correct if necessary
1. Flame sensing electrode and lead connections
2. Electrode position

Flame current should be 1 μA approx.

Replace PCB

Replace PCB

YES

YES

Replace flame sensing electrode

NO

YES

Ensure that mains input terminal L

is Live (230V) and N is Neutral

(0V)

I

Check terminal 1 of ON/OFF/RESET selector is in connection

with PCB - M1 connector terminal 16

Check electrical continuity across terminals 1 & a of

ON/OFF/RESET selector when turned to ‘Reset’ position

Replace ON/OFF/RESET selector

NO

Replace PCB

YES

K

Replace boiler overheat

thermostat

YES

NO

Boiler overheat thermostat operated

or faulty, i.e. continuity across

thermostat terminals

Allow to cool. Continuity across

thermostat terminals more than

1.5 ohm

J

L

Press the reset button on the flue overheat thermostat. If the

boiler does not relight or repeatedly cuts out check the operation

of the flue system or replace the flue overheat thermostat. If the

flue overheat thermostat has not been activated see section ‘D’

Fault Finding Solutions Sections G to L