3.0 Appliance Operation

8

© Baxi Heating UK Ltd 2009

NOTE: All delay timers mentioned in 3.1 and 3.2 are

overridden by domestic hot water demand.

3.1

Central Heating Mode (Fig. 2)

1. With a demand for heating, the pump circulates water
through the primary circuit. At a pre-determined flow
rate the central heating flow switch operates, initiating
the ignition sequence.

2. The main burner ignites at low rate, then the gas valve
controls the gas rate to maintain the heating
temperature measured by the temperature sensor.

3. When the flow temperature exceeds the setting
temperature, a 3 minute delay occurs before the burner
relights automatically (anti-cycling). The pump continues
to run during this period.

3.2

Domestic Hot Water Mode (Fig. 3)

1. Priority is given to the domestic hot water supply. A
demand at a tap or shower will override any central
heating requirement.

2. The flow of water will operate the DHW flow switch
which requests the 3 way valve to change position. This
will allow the pump to circulate the primary water
through the DHW plate heat exchanger.

3. The burner will light automatically and the
temperature of the domestic hot water is controlled by
the temperature sensor.

4. When the domestic hot water demand ceases the
burner will extinguish and the diverter valve will remain
in the domestic hot water mode, unless there is a
demand for central heating.

IMPORTANT: When the selector switch is in the
‘0’ (Off) position the electrical supply to the boiler
is isolated. The boiler will not operate and the
integral timer (if fitted) will require resetting once
the selector switch is turned to either the DHW
or CH position.

1

2

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

3

1

Primary Heat Exchanger

2

Burner

3

Ignition Electrode

4

Flame Sensing Electrode

5

Gas Valve

6

Pump

7

Automatic Air Vent

8

Plate Heat Exchanger

9

Flow Sensor with Filter

10

Pressure Relief Valve

11

Boiler Drain Point

12

Heating Return

13

Cold Water Inlet On/Off Valve and Filter

14

Gas Inlet

15

Domestic Hot Water Outlet

16

Heating Flow

17

Pressure Gauge

18

Hydraulic Differential Pressure Sensor Microswitch

19

Automatic By-Pass

20

Hydraulic Differential Pressure Sensor

21

Diverter Valve Assembly

22

Domestic Hot Water Flow Priority Assembly

23

Domestic Hot Water Flow Priority Microswitch

24

Safety Thermostat

25

Central Heating Temperature Sensor

26

Expansion Vessel

27

Secondary Heat Exchanger

Key

Central Heating Circuit

Domestic Hot Water Circuit

Fig. 3

1

2

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

3

Fig. 2

27

27

Advertising