13.0

Servicing the Boiler

36

© Baxi Heating UK Ltd 2009

13.1

Annual Servicing (Cont)

10. Ease the front edge of the left hand baffle upwards,

disengaging the spring clip. Disengage the tab on the

baffle from the slot in the fan hood (Fig. 56).

11. Undo the screws securing the fan and hood to the

appliance back panel. Draw the assembly forwards

(Fig. 57).

12. Undo the screws securing the burner to the injector

manifold. Draw the burner out of the combustion box,

pulling the electrode grommets from the slots in the

combustion box lower panel (Fig. 58).

13. Disconnect the electrode leads and grommets from

the electrodes. Completely remove the burner (Fig. 58).

14. Brush any deposits from the injectors. Do not use a

pin or wire to clean them.

15. Brush the burner blades and venturis and clean the

combustion box.

16. Ensure that the heat exchanger fins are clear of any

obstruction.

NOTE: If necessary the secondary heat exchanger

may be dismantled - see section 14.24.

DHW Filters (Fig. 60)

17. If the flow of domestic hot water is diminished, it

may be necessary to clean the filters.

18. Initially check the cold water inlet tap filter.

19. Turn the tap off. Undo the blanking cap and remove

the thread bush (Fig. 59).

20. Extract the filter and rinse thoroughly in clean water.

Reassemble and check the flow. If required clean the

manifold filter as described below.

21. Undo the filter cartridge from the inlet/return

manifold.

22. Dismantle the cartridge and carefully remove the

flow regulator and filter gauze. Rinse them thoroughly in

clean water and reassemble in reverse order.

23. Check that the pressure vessel charge is 0.5bar and

reassemble in reverse order of dismantling and

recommission.

24. Turn the selector switch fully anticlockwise against

the spring pressure to the reset position and hold for 2

seconds to reset the boiler.

25. Complete the relevant Service Interval Record

section of the Benchmark Commissioning Checklist at

the rear of this publication and then hand it back to the

user.

Spring Clip

Fan and Hood

Assembly

Baffle

Tab

Burner

Electrode

Grommets

Fig. 56

Fig. 58

Fig. 57

Fig. 59

Threaded

Bush

Cold Water

Inlet Tap

Blanking Cap

Cartridge

Body

Filter Gauze

Flow

Regulator

Venturi

Inlet/Return Manifold

Fig. 60