16.0

Fault Finding

Fault Finding Solutions Sections A to F

Is there 230V at:

Is there 230V at:

Main terminals L and N

Check electrical supply

1.

NO

Main terminal fuse

Replace fuse

Replace PCB

neon

illuminated

2.

YES

Selector terminals a & b and a
& 3. PCB - M1 connector
terminals 9 & 10

Check wiring
Replace selector

3.

NO

NO

A

Pump

Replace pump

1.

NO

PCB - M1 connector terminals 8 & 15

Replace PCB

2.

NO

Change pump supply cable

YES

B

CH system pressure 0.5 to 1.5 bar

Re-pressurise system

1.

NO

Primary flow valve diaphragm damaged

Replace diaphragm

Flow valve rod obstructed

3.

YES

Check the tap of the automatic air
vent is opened

Open the automatic air vent

2.

NO

NO

C

YES

Continuity across flow
microswitch and PCB M2
connector terminals 3 & 4

Replace microswitch

1.

NO

NO

Primary temperature sensor faulty.
Cold resistance approx. 11K ohms
(resistance reduces with increase in temp.)

Replace sensor

2.

YES

Fan connections correct at fan.
PCB - M5 connector, is 230V
across terminals 28 & 29

Fan jammed or faulty winding

Replace PCB

Replace fan

YES

3.

D

If pump jammed, release

Check and correct if necessary
1. Electrical and pressure tube connections
2. Blockage of pressure tubes
3. Restriction in flue
4. Venturi

NO

E

Replace air pressure
switch

Gas at burner

Ensure gas is on and purged

Replace PCB

Replace gas valve

neon illuminated

PCB - M4 connector is approx 230V AC, terminals

36 & 38

YES

Turn selector switch to

‘Reset’ position

YES

NO

NO

NO

F