16.0

Fault Finding

Carry out initial fault finding checks
1. Check that gas, water and electrical supplies are available at the boiler. Electrical supply = 230V ~ 50 Hz.

CH water system pressurised to 0.5 bar when the boiler is cold. The preferred minimum gas pressure is 19.5mbar (natural gas),

or 36mbar (propane).

2. Carry out electrical system checks, i.e. Ground Continuity, Resistance to Ground, Short Circuit and Polarity with a suitable meter.

NOTE: These checks must be repeated after any servicing or fault finding.

3. Ensure all external controls are calling for heat and check all external and internal fuses. Before any servicing or replacement of parts

ensure the gas and electrical supplies are isolated.

Refer to Section 13.1 “Illustrated Wiring Diagram” for position of numbered terminals
Central Heating - Follow operational sequence

Turn selector to

neon illuminated

Primary flow switch operated

Fan runs at max speed

Burner goes out

Turn thermostat

to max.

Pump runs

Air pressure

switch proved

illuminated

Burner on neon

illuminated

Burner output

modulates until set

temperature is reached

Spark at ignition electrodes

for up to 10 seconds

Go to section ‘A’

Go to section ‘B’

Go to section ‘C’

Go to sections ‘J’, ‘L’ & ‘D’

Go to section ‘E’

Replace PCB

Turn selector to the reset

position. If the light does not

extinguish go to sections

H & K

Go to section ‘F’

Go to section ‘I’

Go to section ‘G’

Fan stops

Pump stops

Operation sequence correct

Turn the selector switch to

the ‘Reset’ position and hold

for at least 2 seconds. If

regular resetting is required,

or appliance still does not

operate, investigation is

necessary

External controls and, where

fitted, integral timer calling for

heat

Ensure controls are set to

demand and verify the

contacts are closed

Burner extinguishes

after 10 seconds

YES

YES

YES

YES

YES

YES

YES

YES

YES

NO

YES

YES

YES

YES

NO

NO

NO

NO

NO

NO

NO

NO

NO

YES

NO

NOTE: When instructed to turn the Selector to

the reset position turn the Selector Switch fully

anticlockwise against the spring pressure and hold

for 2 seconds to reset the boiler.