8 troubleshooting, 1 overview, 2 troubleshooting the tank gate interface – Varec TankGate Interface 8315 Series User Manual

Page 101: 1 led displays under normal conditions, Troubleshooting

Advertising
background image

8315 TGI

Troubleshooting

Varec, Inc.

91

8 Troubleshooting

8.1

Overview

This chapter describes the procedures used to isolate hardware faults. Three push-buttons and

eight status Led provide verification of Tank Gate Interface proper operation. If the Tank Gate

Interface is not functioning normally, the user is able to troubleshoot the device by performing

one or more procedures using the three push-buttons. These push-buttons and indicators are

also described in the Motherboard & I/O ExpansL&J Tankwayion Module Configuration chapter.

Caution! Not all troubleshooting instructions are valid for all Communications Modules.

8.2

Troubleshooting the Tank Gate Interface

8.2.1

LED Displays under normal conditions

Operations are normal if the Run, I/O and On-line indicators are flashing.

the table below represents the normal conditions for the Run, Output and

On-line indicators.

Figure 8-1: LED Indicators

Run indicator

The RUN Indicator provides the single most important feedback of proper system operation.

When the system functions properly, the RUN Indicator is constantly flashing at a 0.5Hz rate. If

this indicator ever goes to a steady state condition, either on or off, some malfunction has

occurred. In addition, relative processor loading can be determined by observing the RUN

Indicator duty cycle. Under normal conditions, this indicator flashes once every second.

Communications indicator

The Communications indicator provides communication line status. When it is toggling, the

system is exchanging data. As the system receives a valid message from the Host, this indicator

toggles. If the indicator is idle, the system is off-line.

TXD/RXD LEDs

When these LEDs are flashing, the system is exchanging data between the Tank Gate Interface

and any tank gauge.

Indicator

Condition

Run

Flashes once every second.

Com

Toggles when the system is receiving data. Idle when

not receiving data.

TXD

Every P011 causes the TXD LED to toggle

RXD

Lights when a response is received