2 l&j mcg1200 tank gauge (lj1200), 1 parameters – Varec TankGate Interface 8315 Series User Manual

Page 57

Advertising
background image

8315 TGI

Varec, Inc.

47

5.2

L&J MCG1200 Tank Gauge (LJ1200)

The LJ1200 point provides an interface to the L&J MCG1200 Data Acquisition

Interface. This point provides relay and other interface values to the user. Point and

gauge status information is also available in this point block. This point executes on

the 8315 Tank Gate Interface.

5.2.1

Parameters

The database parameters used by the LJ1200 point are listed and described below:

Configuration Parameters

Function

Tag

A Tag can contain 15 bytes of data and can include any printable ASCII

character. Tags can be used to identify the name of the tank being

monitored The default tag is set to “LJ1200.00”.

Description

A description can contain 30 bytes of data and can include any

printable ASCII character.

FastScanMode

Places the LJ1200 in Fast Scan Mode. Values are Enable or Disable.

ID

Physical Address (0-127). The default is 0.

Mode

Relay Operation Mode. This controls the operation of the LJ1200s 8

relay outputs. Setting the corresponding relay digit sets the coded

variables as seen below.

0: On / Off
1: Close / Open
2: Enable / Disable
3: Active / Inactive
4: Start / Stop
5: Off / On
6: Open / Close
7: Disable / Enable
8: Inactive / Active
9: Stop / Start

Report

Causes automatic notification to the Host (in response to a Change of

State Request) when the Value Changes State. Parameter value can be

High, Low or No. Report=No disables notification. Points with Report =

High will be sent before points with Report = Low. The default is High.

Maxtime

Specifies the maximum time (in secs) between automatic Change of

State data being sent to the Host in response to a Change of State

Request. Report must be set to either Low or High for the Value

parameter to be sent in response to a Change of State Request. A value

of 0 disables this option. Non-zero values cause responses to be sent

even if the value has not changed since the last message. The

maximum is 255 seconds. The default is 240.

Watchdog

Enables the watchdog task on the Motherboard. The watchdog task

monitors the LJ1200 point on the Model 8215 and verifies it is

scanning for gauges. If the Model 8215 fails, the 0x4000 and the

0x0010 bits of the PntStatus will be set to indicate the failure.