Varec TankGate Interface 8315 Series User Manual

Page 38

Advertising
background image

Software Description

Tank Gate Interface

28

Installation and Operations Manual

In this example, the Modbus register map is configured according to the following table:

Table 4-2:

Example Modbus register map

Data Address

Parameter

Comments

100-101

MSTX.00.Level

Level is in IEEE Floating point format.

102-103

MSTX.01.Level

104-105
.
.
.
138-139

MSTX.02.Level
.
.
.
MSTX.19.Level

200-201

MSTX.00.Temp

Temperature is in IEEE Floating Point

Format.

202-203

MSTX.01.Temp

204-205
.
.
.
238-239

MSTX.02.Temp
.
.
.
MSTX.19.Temp

300

MSTX.00.PntStatus

PntStatus is in Integer format.

301

MSTX.01.PntStatus

302
.
.

.

.319

MSTX.02.PntStatus
.
.

.

.MSTX.19.PntStatus

Advertising