8315 TGI

Varec, Inc.

59

gauges are read from the Fast Scan List. When a Normal Scan Cycle occurs, gauges are read

from the Normal Scan List.

The RKSCN point provides the ability to control the operation of the Fast Scan List. The RKSCN

point has several parameters that involved:

The number of gauges scanned during a Fast Scan Cycle is determined by the FastScanMax. If

the value is 0, then all L&J device points with the FastScanMode set to Enable will be scanned.

The Interleave parameter controls the number of gauges read during each Normal Scan Cycle.

Example – Default method, with 1 tank in the Fast Scan List

Interleave = 1, FastScanMax=0, FastScanTime=00:00:00, LJ2000.00.FastScanMode = Enable (ID

= 1).

Example –1 tank in the Fast Scan List

Interleave = 3, FastScanMax=0, FastScanTime=00:00:00, LJ2000.00.FastScanMode = Enable

Example – 6 tanks in the Fast Scan List

Interleave = 3, FastScanMax=2, FastScanTime=00:00:00, LJ2000.00.FastScanMode = Enable

Parameter

Description

Interleave

Number of points to scan during each Normal Scan Cycle

FastScanMax

Number of points to scan during each Fast Scan Cycle

FastScanTime

If defined, the FastScanTime is used to determine when Fast Scan

Cycles are performed

NumFastScan

Number of points in the Fast Scan List

(Fast Scan shown in shaded cells)