8315 TGI

Varec, Inc.

51

Scanning

Scanning begins when the Module is assigned. The DevType must match the configuration of

the transmitter. Conversion from English to Metric can be performed be setting the LevelConvert

and the TempConvert parameters in the LJSCAN point associated with the LJ1500 point.

Filtering

Filtering is performed using the LevelFilter and TempFilter parameters of the associated LJSCAN

point. If a change in level greater than the LevelFilter is read from the gauge, the Level parameter

is not updated until it has stabilized. A reading is considered stable if it does not change more

than the LevelFilter value for the number of readings determined by the Filter parameter. Thus,

small changes (less than the LevelFilter) result in the Level being updated immediately. Large

changes must pass through the filter and will not be seen until the reading stabilizes. The same

strategy is applied to the Temp parameter value using the TempFilter parameter. Since the

LevelFilter and TempFilter are associated with the LJSCAN point, it applies to all LJ1000 and

LJ1500 points. The number of readings used in the filter algorithm can be set on an individual

basis. If no filtering is desired, set the Filter parameter to 0.

Time-out

A separate time-out mechanism is employed to assure that the filter does not prevent a reading

from taking place. The LJSCAN parameter ScanTimeout is used to set an alarm bit in the

PntStatus parameter if a good reading does not take place in a specified period of time. If there

is no response from the gauge, or if there are constant parity errors, or if the level is constantly

changing by a value greater than the LevelFilter, then the 0x02 bit of the PntStatus will be set

after the ScanTimeout period elapses. The ScanTime parameter in the LJ1500 point is updated

each time a good reading takes place. If the ScanTime differs from the Elapse parameter by more

than the ScanTimeout, the 0x02 bit is set in the PntStatus.