8315 TGI

Hardware

Varec, Inc.

7

2.2.1

Power Supply

Unit AC Power terminal block (J2)

Surge Protection terminal block (J4)

Field Power terminal block (J3)

Auxiliary DC Power Output terminal block (J8)

AC Power fuses (500 mA - 250V 5x20 mm) (F1, F2)

Field Voltage Selection Jumper (W3)

2.2.1.1 Unit AC Input Power terminal block (J2)

The Unit AC power terminal block is used to provide AC power to the Tank Gate Interface. The

power requirements for the Tank Gate Interface are 100-240 VAC, 50/60 Hz. The AC Input

Power terminal block is shown in the figure below.

Figure 2-4: AC Input Terminal Block

2.2.1.2 Surge Protection (Surge Gnd) terminal block (J4)

The Surge Gnd terminal block is used to connect the surge protection components (gas tubes,

MOVs) to earth ground. Ensure there is a low impedance path (< 1ohm) to earth ground (a

ground rod or grounding system).

EARTH

NEUTRAL

LINE

SURGE GND

+

-

VFIELD

J2

J4