1 id dip switch (sw1), Closed open – Varec TankGate Interface 8315 Series User Manual

Page 26

Advertising
background image

8215 L&J Tankway Communications Interface Module

Tank Gate Interface

16

Installation and Operations Manual

Figure 3-1: L&J Tankway Tank Gate Interface Module

3.2.1

ID DIP Switch (SW1)

The dip switch is used for setting the ID number (1-14). The ID is a binary number representing

the address of the 8317 TGI.

Table 3-1:

ID DIP Switch settings

Field wiring
terminal block (J3)

LED indicators (D1 – D6)

Surge/Shield
ground connector (J4)

External Power Connector
(+48 - 65 VDC) (J2)

+48-65 VDC power fuse
(1 A 250V TR5) (F1)

ID DIP Switch (SW1)

Transmit Line Fuse
(63 mA 250V TR5) (F2)

Firmware

Binary

8

4

2

1

Binary

8

4

2

1

Switch #

1

2

3

4

Switch #

1

2

3

4

Address 1

o

o

o

c

Address 8

c

o

o

o

Address 2

o

o

c

o

Address 9

c

o

o

c

Address 3

o

o

c

c

Address 10

c

o

c

o

Address 4

o

c

o

o

Address 11

c

o

c

c

Address 5

o

c

o

c

Address 12

c

c

o

o

Address 6

o

c

c

o

Address 13

c

c

o

c

Address 7

o

c

c

c

Address 14

c

c

c

o

Address 1 Shown