4 grounding, 5 installing communications – Varec TankGate Interface 8315 Series User Manual

Page 74

Advertising
background image

Installation

Tank Gate Interface

64

Installation and Operations Manual

6.3.4

Grounding

To allow use in harsh industrial environments, the Tank Gate Interface incorporates ANSI/IEEE

surge protection. In solid-state control systems, grounding helps limit the effects of noise due

to electromagnetic interference (EMI) and provides additional surge protection when high

voltage switching circuits are connected to the unit. The grounding path for the Tank Gate

Interface and its enclosure is provided by the equipment grounding connector. The resistance

from the Tank Gate Interface ground to the grounding electrode must not exceed 1 ohm.

Additional ground wires should be connected as required for each I/O module.

Caution! All applicable codes and ordinances must be observed when wiring the Tank Gate

Interface.

6.3.5

Installing Communications

6.3.5.1 RS-232 Communications

To install the RS-232 communication option, connect an RS-232 cable to connector J7

(COM0).

Note The 8311 TGI only supports communication on COM0.

6.3.5.2 Power-Up

Before the field cables are attached, perform an initial system verification.

6.3.5.3 Initial system verification

Connect the power cable to power connector P1, then connect an RS-232 cable from a PC

with ViewRTU to J7 (COM0).

Power up the unit.

The CPU LED on the tank gauge interface module should toggle on and off. If the CPU indicator

is not flashing, turn off system power and proceed with the Troubleshooting and Calibration

chapter.

6.3.5.4 Establishing Host Communications

When the main system power is turned on, the Host communications status is set to On-line by

default. The Tank Gate Interface then waits for a valid poll from the Host computer. If the

communication cable is installed and the Host is running, a communications link is established.

Verify this condition with a hand-held terminal or ViewRTU.

6.3.5.5 Verifying Host Communications

Display the COM Point and verify that an On-line condition is indicated.