4 performing a hard reset – Varec TankGate Interface 8315 Series User Manual

Page 103

Advertising
background image

8315 TGI

Troubleshooting

Varec, Inc.

93

8.2.4

Performing a Hard Reset

A ‘Hard Reset’ clears the Tank Gate Interface’s database. The following procedure describes the

steps necessary to perform a Hard Reset:

1. Set the ID DIP switch to 15 (all switches Closed/On). This action initiates the Hard Reset

Procedure.

Figure 8-1: Set the ID DIP switch to 15

2. Press the Reset button

Figure 8-2: Switches SW3 on the Tank Gate Interface motherboard

3. The Tank Gate Interface will perform its memory test. When it has completed the memory

test, all LEDs will be on.

4. Set the ID DIP Switch to the desired address (1-14). At this point, there is no further action

required by the user.

Figure 8-3: Set the ID DIP switch to the desired addresses

ID = 15

RESET

SW3

EARTH

NEUTRAL

LINE

SURGE GND

A/TXD

B/RXD

GND

RTS

CTS

TXD

RXD

GND

+15V

+5V

GND

-15V

+

-

VFIELD

COM1

COM 0

AUX POWER

VFIELD=48V

VFIELD=24V

RESET

RS232

RS485

COM1

HARDWARE HANDSHAKING

A

B

ID = 1