2 led indicators (d1-d6), 3 external power connector (+48v) (j2), 4 surge/shield ground connector (j4) – Varec TankGate Interface 8315 Series User Manual

Page 27: 5 field wiring terminal block (j3)

Advertising
background image

8315 TGI

8215 L&J Tankway Communications Interface Module

Varec, Inc.

17

3.2.2

LED Indicators (D1-D6)

The LED displays indicate the status of the Model 8315’s CPU and

communications. The indicators are identified in the following figure.

CPU: CPU activity

COM: Communication between the TankGate and the host computer

TXD: Transmitting data to tank gauge

RXD: Receiving data from tank gauge

+5V: Indicates interface module power

+VEXT: Indicates external power

Figure 3-2: LED Indicators

3.2.3

External Power Connector (+48V) (J2)

Connect the +48 VDC External Power as shown

below:
Figure 3-3: External Power Connector

3.2.4

Surge/Shield Ground Connector (J4)

Connecting the Surge/Shield ground connector

Caution! This ground connection is important for system safety.

Connect a 14 AWG copper wire between the ground terminal (J4) and a good earth ground.

Perform this step before connecting ANY other wires.

Verify that the resistance in this connection does not exceed 1 ohm.

3.2.5

Field Wiring terminal block (J3)

A schematic illustrating the terminal connections of the Model 8315 is shown below: