8315 TGI

Varec, Inc.

57

5.5

L&J Scanner (LJSCAN)

The L&J Scanner point is used in conjunction with L&J Tank (LJ1000, LJ1500 and

LJ2000) gauge points. This point provides dynamic and statistical data for the 8315

Tank Gate Interface and L&J tank transmitters.

5.5.1

Parameters

The database parameters used by the LJSCAN point are listed and described below:

Configuration Parameters

Function

Module

Model 8215 module address

Interleave

Number of Normal Scan Points to scan between Fast Scan Cycles. Refer

to Fast Scan discussion below.

FastScanMax

Max Number of Fast Scan points to scan each Fast Scan Cycle. Refer to

the Fast Scan discussion below.

FastScanTime

Time between Fast Scan Cycles. If 0:00:00 (default), Fast Scan Cycles

are determined using the Interleave and FastScanMax parameters.

Refer to the Fast Scan discussion below.

MaxRetry

Value between 1-10 indicating the number of times the scanner will

attempt to poll a tank transmitter that has not responded. Default is 2.

Timeout

Value between 0-30000 indicating the number of milliseconds the

scanner will wait for a response from a tank transmitter. Default is

2000.

ScanDelay

Value between 0-30000 indicating the number of milliseconds the

scanner will delay between each poll. Default is 500.

LevelConvert

Determines the units in which the level data will be displayed. F: feet,

M: Meters m: Millimeters.

TempConvert

Determines the units in which the temperature data will be displayed.

F: Fahrenheit, C: Celsius.

LevelFilter

Value used by LJ1000, LJ1500 and L2000 points for filtering level

changes

TempFilter

Value used by LJ1000, LJ1500 and LJ2000 points for filtering

temperature changes

HoldOff

Gauge down holdoff count. The HoldOff is used to reduce the number

of scan requests issued to a gauge that is not responding.

ScanTimeout

Time value used to set an alarm bit in the PntStatus parameter of

LJ1000, LJ1500 and LJ2000 points for gauges that are not responding

or responding with errors.

Dynamic Parameters

Function

ScanCmd

Allows the user to Enable, Disable, or Reset Scanning.