2 application – Varec TankGate Interface 8315 Series User Manual

Page 58

Advertising
background image

Tank Gate Interface

48

Installation and Operations Manual

5.2.2

Application

The LJ1500 point provides an interface to the L&J MCG1200 Data Acquistion Interface. L&J Model 1200
are connected directly to a Model 8215 Tank Gauge Interface Module. The Model 8215 is automatically
detected at startup, and an LJSCAN point is automatically created to manage the scanning task.

The ID must match the unit address of the MCG 1200.

Dynamic Parameters

Function

Command_0 through

Command_7

The state of the 8 LJ1200 relays. The coded variable output is set via

the Mode parameter.

WriteCmd

Output Value for Relays

CmdStatus

Status of Last Command

Value

Value of the LJ1200 Contact Input

PntStatus

Integer HEX value indicating status of point. Values are:
0x0002: Scan Timeout
0x0010: Gauge Not Responding
0x0020: Blown Transmit Fuse
0x0040: Parity Error
0x0080: Tankway Error
0x4000: Failure of the Model 8215. This bit is set if the Watchdog task

on the Motherboard determines that the Model 8215 has stopped

updating.

AlarmTime

Time that alarm first occurred. The point is in alarm when the

PntStatus is non zero.

Elapse

Time of the last scan.

ScanTime

Time of the last good reading. A reading is considered good if it has no

parity or time-out error, and has passed the filter criteria.

Raw1

Raw data from gauge. Value reported as hexadecimal value.

PntCheckSum

CRC-16 Checksum for point's static Configuration Parameters.