Tank Gate Interface

58

Installation and Operations Manual

5.5.2

Application

The LJSCAN point monitors the status of the Model 8215 Tank Gauge Interface. The LJSCAN

point is created automatically by the Model 8215. The point number will correspond to the

Module such that LJSCAN.1 is created for module 1 (the 8215’s unit address DIP switch = 1). Use

the Upload command to retrieve the data from the LJSCAN point or any other points created

automatically by the 8300 TGI.

The NumRequests parameter gives the total number of requests attempted, while the

NumTimeouts and NumComErrors are the number of time-outs and communications errors.

The ID is the current gauge ID being scanned. The Pnt parameter is the Tag of the LJ1000,

LJ1500 or LJ2000 point associated with the point being scanned.

This point can set the type of engineering units for the level and temperature data (English or

Metric). By setting the LevelConvert and TempConvert the Level and Temp can be changed from

English to Metric or vice-versa. If the LevelConvert and TempConvert are not set, no conversion

will be performed.

The user can also set the delay between each poll as well as how long to wait for a transmitter

to respond. If a transmitter is not responding, it will no be polled as often as transmitters that

are on-line. The HoldOff parameter determines how often the off-line transmitter will be polled.

For example, if the HoldOff is 10, then a transmitter that is off-line will be polled only one tenth

as often as a transmitter that is on-line.

The ScanTimeout parameter is used by LJ1000, LJ1500 and LJ2000 points to determine if there

have been no good readings for a specified period of time.

5.5.3

Fast Scan

The L&J device points have a parameter called the FastScanMode. Setting the FastScanMode to

Enable places the L&J device point in the Fast Scan List. Points in the Fast Scan list are polled

more frequently than points that are in the Normal Scan List. Scanning of tank gauges alternates

between points from the Fast Scan List and the Normal Scan List. When a Fast Scan Cycle occurs,

ID

Address of gauge currently being scanned

Cmd

Command currently being sent to the gauge

Pnt

Point currently being executed

NumRequests

Number of gauge polls since last reset

NumComErrors

Number of gauge polls which resulted in an error.

NumTimeouts

Number of unresponded requests issued before the scanner timed out.

NumScanList

Number of points in the Scan List

NumFastScan

Number of points in the Fast Scan list (i.e., the number of EN854 points

with FastScanMode set to Enable) Refer to the Fast Scan discussion

below.

PntStatus

Byte value indicating status of point. Values are:
0: No Error

PntCheckSum

CRC-16 Checksum for point’s static Configuration Parameters

Dynamic Parameters

Function

Advertising