Software Description

Tank Gate Interface

32

Installation and Operations Manual

Application

The Emulator point (EMU) provides a communication interface between older tank gauging

system and point blocks within the 8203 Dual RS-485 Communications Interface Module .

Currently, the 8203 Dual RS-485 Communications Interface Module can emulate a Whessoe

Varec Model 6810 Tank Scanning Unit (TSU).

The EMU point associates a tank gauge point with an address to by used by TankView. EMU.0

provides point references for TankView System Addresses 1-50. EMU.1 is associated with

System Addresses 51-100. A EMUGW gateway point is automatically created when the protocol

for a COM point is set to TSU Slave.

TempUnits

Specifies the engineering units for the temperature data.
TempUnitsSpecifies the engineering units for the temperature data.
F: Fahrenheit
C: Celsius
The TempUnits needs to match the units specified during the gauge

setup.

DensityUnits

Specifies the engineering units for the density data.
DensityUnitsSpecifies the engineering units for the density data.
K: kg/m3
A: API
L=lbs/cu ft
The DensityUnits needs to match the units specified during the gauge

setup.

Offset

Specifies the offset to the first address.

PntRef1 - 20

Input point reference for the EMU point to monitor. The PntRef parameter

is set to the Level parameter for the tank gauge point. The temperature

will be read at the same time as the level. The EMU point interfaces tank

gauge interface points:
WV1900 - Whessoe-Varec Model 1900

Dynamic Parameters

Function

PntStatus

Byte value indicating status of point Values are:
Dynamic ParametersFunction
PntStatusByte value indicating status of point Values are:
0: No error
15: Invalid Type for PntRef
16 Invalid Number for PntRef
17 Invalid Param for PntRef
19: PntRef point does not exist
25: PntRef is not defined

PntCheckSum

CRC-16 Checksum for point's static Configuration parameters.