1 l&j mcg1000 tank gauge (lj1000), 1 parameters – Varec TankGate Interface 8315 Series User Manual

Page 53

Advertising
background image

8315 TGI

Varec, Inc.

43

5.1

L&J MCG1000 Tank Gauge (LJ1000)

The LJ1000 point provides an interface to L&J MCG1000 Tank Gauge transmitters.

This point provides both level and temperature data. Point and gauge status

information is also available in this point block. This point executes on the Model

8315 Tank Gate Interface.

5.1.1

Parameters

The database parameters used by the LJ1000point are listed and described below:

Configuration Parameters

Function

Tag

A Tag can contain 15 bytes of data and can include any printable ASCII

character. Tags can be used to identify the name of the tank being

monitored The default tag is set to “LJ1000.00”.

Description

A description can contain 30 bytes of data and can include any

printable ASCII character.

FastScan

Places the LJ1000 in Fast Scan Mode. Values are Enable or Disable.

ID

Physical Address (0-127). The default is 0

DevType

Tank Gauge Type.
DevType Tank Gauge Type.
DevType = 1 Uses a gray code table for CCW Varec gauges
DevType = 2 Uses a gray code table for CCW S&J gauges
DevType = 3 reports data in feet and hundredths of a foot
DevType = 4 reports data in 32nds of inches

Filter

Gauge data filter constant. The Filter is used when scanning data from

an L&J gauge. A buffer is maintained for the last 8 readings. The Filter

determines how many of the reading in the buffer are used when

calculating the Level and Temp parameters. If all of the level readings

are within a deadband determined by the LJSCAN LevelDeadband

parameter, then the Level reading is updated with the latest data. If a

large change is detected (data changed more than the LevelDeadband),

then the Level is not updated until the change between readings is less

than the LevelDeadband. The default is 3.

LevelOffset

Specifies the amount of offset to add to the Level. The default is 0.

TempOffset

Specifieds the amount of offset to add to the Temp.

The default is 0.

TempDeadband

Change of State Temperature deadband value. This parameter is used

when the Report is High or Low to determine if a change of state has

occurred. This parameter does not affect the Temperature parameter

value, only if it is automatically sent to the Host system.

LevelDeadband

Change of State level deadband value. This parameter is used when the

Report is High or Low to determine if a change of state has occurred.

This parameter does not affect the Level parameter value, only if it is

automatically sent to the Host system.

Report

Causes automatic notification to the Host (in response to a Change of

State Request) when the Value Changes State. Parameter value can be

High, Low or No. Report=No disables notification. Points with Report =

High will be sent before points with Report = Low. The default is High.