Function overview – Xantrex Technology Xantrex Battery Monitor User Manual

Page 13

Advertising
background image

4

Please note that regularly (at least once per month) fully charging

your battery not only keeps it synchronized with the Xantrex Battery

Monitor, but also prevents substantial capacity loss of your battery,

limiting its lifetime.

Function overview

The Xantrex Battery Monitor factory settings are suitable for an

average 12 V lead acid battery system of 200 Ah. So in most cases

when monitoring a 12 V system, the only Function which may need

to be changed is the battery capacity (F01). When using other types

of batteries, please ensure that you know all the relevant

specifications to properly set up the Xantrex Battery Monitor

Functions.
You can fully adjust your Xantrex Battery Monitor with the help of

20 different settings, or “Functions.” Before setting up the Xantrex

Battery Monitor, you must activate the setup mode first. The setup

mode can be activated by pressing the SETUP key for three seconds.

The display will blink to indicate that the setup mode is active. The

desired Function can be selected by repeatedly pressing the SETUP

key. The selected Function is represented as Fxx where xx indicates

the Function number. The < and > keys can be used to alter the value

of the selected Function. The next Function can be selected by

pressing the SETUP key again. To save the changed settings to the

Xantrex Battery Monitor memory, press the SETUP key for three

seconds until the display stops flashing and the battery monitor

jumps back to normal operating mode again. If the Xantrex Battery

Monitor operates in the setup mode and not a single key is pressed

for 90 seconds, the monitor will jump back to normal operating

mode automatically, without saving the altered settings.
The table below gives an overview of all Xantrex Battery Monitor

Functions, including a short description. For most battery systems,

adjusting the values of Functions F01, F02, F03, F07 and F08 should

be sufficient. It is recommended not to change the Functions F04,

F05, F06, F09, F10, F11, F12, F13, F14, F15, F16, F17, F18 and F20

when in doubt.

F01

Battery capacity in amp hours (Ah). This must be the

capacity at a 20h discharge rate and 20 °C (68 °F).

Default

Range

Step size

200 Ah

20 – 2000 Ah

1 Ah