6

F06

Low-battery alarm OFF. When the state-of-charge

percentage has risen above this value and the alarm relay

is activated, the alarm relay will be deactivated again.

When FULL is selected the alarm relay is deactivated

when the charged parameters are met.

Default

Range

Step size

80.0%

0.0 – 100.0% /

FULL

1.0%

F07

Under-voltage alarm. When the battery voltage falls

below this value, after 10 seconds the message Lo will

appear on the display and the alarm relay will be

activated.

Default

Range

Step size

10.5 V

OFF / 8.0 – 33.0 V

0.1 V

F08

Over-voltage alarm. When the battery voltage rises above

this value, after 5 seconds the message Hi shall appear on

the display and the alarm relay will be activated.

Default

Range

Step size

16.0 V

OFF / 10.0 – 35.0 V

0.1 V

F09

Charge efficiency factor (CEF). It is recommended to

keep this value at AU (automatic calculation). The value

A90 resets the automatic calculation to 90%. A manual

setting is represented by Uxx where xx is the charge

efficiency. (See page 2 for more info about CEF.)

Default

Range

Step size

AU

U50 – U99 / AU /

A90

1%

F10

Peukert exponent (discharge efficiency). When unknown

it is recommended to keep this value at 1.25. A value of

1.00 disables the Peukert compensation. Call Customer

Service or your battery manufacturer before changing

this setting.

Default

Range

Step size

1.25

1.00 – 1.50

0.01