Battery temperature. In this Function the average battery

temperature can be adjusted. The value AU enables the

automatic temperature measurement provided that an

external temperature sensor is connected to the Xantrex

Battery Monitor. Also the temperature readout in normal

mode is enabled. When AU is selected and the connection

with the temperature sensor is lost, four dashes (- - - -)

are displayed and the internal temperature compensation

calculations are made using the default 20 °C value. This

Function can only be set in °C. Use the following

formulas to convert °C to °F : T(

°F

) = (T(

°C

) x 1.8) + 32

and T(

°C

) = (T(

°F

) – 32) / 1.8.

Default

Range

Step size

20 °C

0 – 50 / AU

1 °C

F12

Temperature coefficient. This is the percentage the

battery capacity changes with temperature. The unit of

this value is “%cap/°C” or percent capacity per degree

Celsius. The default setting is 0.5 %cap/°C, which is

typical for most batteries. The setting OFF disables

temperature compensation.

Default

Range

Step size

0.5 %cap/

°C

OFF / 0.05 – 0.95

%cap/ °C

0.05 %cap/ °C

F13

Time-to-go averaging period. Specifies the time window

in minutes the moving averaging filter works with.

Selecting the right time depends on your installation. A

value of 0 disables the filter and gives you instantaneous

(real-time) readout; however, the displayed values may

fluctuate heavily. Selecting the highest time (12 minutes)

ensures that long term load fluctuations are included in

the time-to-go calculations.

Default

Range

3 minutes

0 / 3 / 6 / 9 / 12 minutes