Current threshold. When the measured current falls

below this value it will be considered as zero amps. With

this function it is possible to cancel out very small

currents which can negatively affect long-term state-of-

charge readout in noisy environments. For example if an

actual long-term current is +0.05 A and due to injected

noise or small offsets the battery monitor measures

–0.05 A, in the long term the Xantrex Battery Monitor

can wrongly indicate that the battery needs recharging.

In this case set Function 14 to 0.1. The Xantrex Battery

Monitor calculates with 0.0 A so that no wrong

assumptions can be made. A setting of 0.0 disables this

Function.

Default

Range

Step size

0.0 A

0.0 – 2.0 A

0.1 A

F15

Temperature unit selection. This Function enables

selection between degrees Celsius (°C) and degrees

Fahrenheit (°F) temperature readout.

Default

Range

°C

°C, °F

F16

Voltage prescaler. This Function is only important when

an optional prescaler is installed on the battery voltage

sense input of the Xantrex Battery Monitor. The voltage

charged parameter, under-voltage and over-voltage

alarm settings are linked with this Function. Don’t

change this value when you are not using a prescaler!

Default

Range

1-1

1-1 / 1-5 / 1-10