Set-up of a signal conditioning instrument VEGAMET 614

For the adjustment with medium you have to
know the actual level in percent and it should
be possible to modify the level.

If e.g. the vessel is empty, click to

Min-

Adjustment. Enter in the appropriate field
"0,0“. Then click to

Save. The Min-adjust-

ment is carried out and you return to the
window "Min-/Max-Adjustment“.

When the vessel is full, choose

Max-Ad-

justment, enter in the appropriate field
"100,0“ and click to

Save.

The min. and max. adjustment with medium
can be also carried out with levels of e.g.
25 % and 80 %. The difference of the adjust-
ment points however should be as big as
possible.

If you have chosen in the window "Adjust-
ment“

Adjustment without medium, the win-

dow appears in which you enter the
appropriate pressure values for 0 % and
100 %-filling. Then click to

OK and then to

Quit. You now have again the window "Instru-
ment data parameter adjustment“ in front of
you.