Technical specifications, 1. astat, Cd plus, general specifications – GE Industrial Solutions ASTAT-CD Plus User Manual

Page 10

Advertising
background image

Voltage Ratings

3ph AC Systems

Up to 500V, +10%, -15% for QC2xDP ASTAT-CD Plus series

Freq. Range

50/60

Hz

Control range of 45-65 Hz

Control

Control system

Digital system with microcontroller

Specifications

Starting ramp with progressive increase in voltage and current limitation

Initial voltage (pedestal)

%

30 - 95 Un

Starting torque

%

10 - 90 Mdirect start

Kick start

%

95 Un (90% Mdirect start), adjustable 0 to 999 ms

Motor unit ratio (N)

0.4 - 1.2

Current limit (starting)

1 to 4.5 (Ir/In) Max 7.0 In

Acceleration ramp time

s

1 to 99 (types: standard or linear ramp up)

Energy savings

Output voltage reduction according to power factor

Override

Fixed output voltage permanently equal to supply voltage

Bypass

Direct control of a bypass contactor

Brake time by ramp

s

1 to 120 (1 to 99 in secondary ramp) adjustable independently of starting ramp time (types: standard,

pump control or linear ramp down)

DC braking

0 to 99 s.; 0.0 to 2.5xIn

Slow speed

Direct torque: 7% or 14% of nominal speed; reverse torque: 20% of nominal speed

Retry

0 to 4 attemps, and 1 to 99 sec. retry time

Monitoring

Motor current, line voltage (1), power, power factor and elapsed time

Running

External control

Start - Stop

Acceleration phase

Adjustable time

Permanent phase

Energy savings / Override choice

Stop phase

Power cut-off / Ramp / DC braking/Pump control

Inputs / Outputs

Inputs

4 digital optocoupled. Two fixed (Start , Stop), and 2 programmable (I3, I4)
1 Analog 0-5VDC for Tachogenerator input feedback

Outputs

3 programmable relays (1r, 2r, 3r)
1 Analog 0-10VDC output for current metering

Protections

Current limit

Adjustable from 1 to 4.5 (Ir/In) Max 7.0 In

Overload

IEC class 10 and 20 ; NEMA class 10, 20 and 30 all selectable

Cool-down time after
overload trip

s

300 for reset

Loss on input phase

s

Trip at 3

Thyristor short circuit

ms

Trip at 200

Heatsink overheating

ms

Trip at 200

Motor thermistor

ms

Trip at 200 if thermistor impedance > response value

Loss on output phase

s

Trip at 3

Stalled rotor

ms

Trip at 200

Supply frequency error

Hz

If f < 45 or f > 65, will not start

Overcurrent

100 to 150% In; trip time adjustable from 0 to 99 sec.

Undercurrent

0 to 99% In; trip time adjustable from 0 to 99 sec.

Overvoltage (1)

100 to 130% Un; trip time adjustable from 0 to 99 sec.

Undervoltage (1)

0 to 50% Un; trip time adjustable from 0 to 99 sec.

Error (CPU)

ms

60

Memory

4 former errors

Long start time

s

2 x ta (ta = acceleration ramp time)

Long slow speed time

s

120

Environmental

Temperature

°C

0 to +55 (derate output current by 1.5% / °C above 40°C)

conditions

Relative humidity

%

95% without condensation

Maximum altitude

m

3000 (derate output current by 1% / 100m above 1000m)

Mounting position

Vertical

Protection Degree

IP00, UL Open

Standards

CE, cUL, UL

CE Conforming IEC 947-4-2; UL, cUL conforming to UL508

Conducted & radiated emissions

Conforming IEC 947 -4-2, Class A

Electrostatic discharges

Conforming to IEC 1000-4-2, level 3

Radioelectric interference

Conforming to IEC 1000-4-6, level 3 and to IEC 1000-4-3, level 3

Immunity to fast trasients

Conforming to IEC 1000-4-4, level 3

Immunity to Surge Voltage

Conforming to IEC 1000-4-5, level 3

3-1. ASTAT

®

-CD Plus, General specifications

3. Technical Specifications

3-1

Note: (1) Monitors L1

I

Actual measured motor current

Im

Maximum starting current desired

In

Nominal motor nameplate FLA

Ir

ASTAT rated nameplate FLA

L

Current limit for starting Im/Ir

Lmax

450/N

Mdirect start Full voltage starting torque
N

In/Ir

SF

Service factor

Un

Full line voltage

Abbreviations

ASTAT CD 9/13