Programming, 3. monitor block parameters – GE Industrial Solutions ASTAT-CD Plus User Manual

Page 19

Advertising
background image

4-3. Monitor block parameters

Function

Display

Status

Motor current

Software version

Main source voltage (1)

Power factor

Line power

Elapsed time

Error trace buffer

Password

E2PROM writing

Parameter display
selection

4. Programming

O N

M x x x

v x x x

V x x x

P F x x

w x x x

E x x x

e x x x

K x x x

W x x x

G x x x

Description

Switch on time. Equipment is connected to main supply
Stop
Remote control through serial port
Kick start
Acceleration ramp
Full conduction / Override (full voltage)
Energy saving
Soft stop
Pump control
DC braking
Inching / slow speed
Linear ramp (tacho feedback needed)

Displays motor current in Amps.
Current higher than 999A is displayed in kA.
If parameter UFxx is not calibrated, the motor current is
displayed in % In

xxx = Version number.

Displays line voltage in Volts.

Displays line Power Factor.

Displays Line Power.

Displays RUN time in Hours (x 1000)

Saves the last four errors:
e0xx:

Fault 1 -Latest fault- xx: Fault code error

e1xx:

Fault 2

e2xx:

Fault 3

e3xx:

Fault 4

= 69

allows E2PROM writing operation

= 10

Key lock enabled

= 20

Key lock disabled

Saves the unit current parameters to the E2PROM.
This rewrites the last values saved. (Password 69 required)

CAL:

Displays Calibration Parameters

BAS:

Displays Basic Parameters

ADV:

Displays Advanced Parameters

ALL:

Displays All parameters

4-4

Default

Range

Unit

ON

STOP

LOCK

PULS

RAMP

FULL

SAVE

SOFT

PUMP

DCBK

INCH

TACH

000-999

1.0-9.9

-

-

00-99

-

-

e0xx-e3xx

000-999

ON, OFF

CAL, BAS, ADV,

ALL

O N

K 0 0 0

W O F F

G B A S

-
-
-
-
-
-
-
-
-
-
-
-

A

kA

%

-

V

%

kW

Hrs

-

-

-

-

Note:

(1) Monitors L1

Advertising