3. Technical Specifications

3-2. I/O Terminal board specifications

Power I/O terminals
Terminal

Function

Description

1L1, 3L2, 5L3

Mains Input

3ph input voltage 200-480 volts QC2xxx type

2T1, 4T2, 6T3

Motor output

Output terminals to 3ph AC motor

A1, A2, B1, B2

Input Control Voltage

110/120V AC, +10%, -15%

220/240V AC, +10%, -15%

Digital Inputs
Terminal

Function

Description

57

Common for digital inputs

This is a common terminal for the digital input terminals specified below.

1

Run

Run order. Command signal may be provided by one NO dry momentary contact to terminals 1 and 57.

2

Stop

Stop order. Command signal may be provided by one NC dry momentary contact to terminals 2 and 57.

NOTE:

Run/Stop permanent command allows linking 1-57 and using one dry NO contact to 2-57
terminals.

3

Programmable input I3

These two inputs are programmable. They can be assigned to the following internal functions:

4

Programmable input I4

-soft stop

-DC brake

-Linear ramp

-pump control

-slow speed control

-dual ramp selection

-kick start

-reverse slow speed

-bypass function

-override

-local / remote control

Command signal should be provided by one NC dry contact to terminals 57-3 or terminals 57-4. By switching
this contact ON / OFF it is possible to enable or disable the assigned function.

Digital Outputs
Terminal

Function

Description

11, 12, 14

Programmable relay 1r

11-12 = NC, 11-14 = N.O. dry contacts. This relay can be assigned to several internal output functions (p. 3.6).
As default assigned to function RUN

23, 24

Programmable relay 2r

23-24 = N.O. dry contact. This relay can be assigned to several internal output functions (page 3-6).
As default assigned to function EOR

33, 34

Programmable relay 3r

33-34 = N.O. dry contact. This relay can be assigned to several internal output functions (page 3-6).
As default assigned to function DC BRAKE
Common for all relay output contacts

Maximum usage voltage:

380VAC (B300-UL)

Thermal current:

8A

AC-15 use:

220V / 3A, 380V / 1A

DC-15 use:

30V max/ 3.5A

Analog I/O
Terminal

Function

Description

8

Analog input common (-)

This is a common terminal for the analog input terminal number 7 and analog output terminal number 9.

7

TG feedback input (+)

0-5V analog input for speed feedback. It should be provided by a DC tacho-generator coupled to the motor.
This speed feedback signal is required when the "linear ramp" function is used.

9

Current output (+)

0-10V DC analog Output for current measurement purpose. (1 x Ir = 2V DC output)
Load Impedance 10K

or higher.

Motor thermistor terminals
Terminal

Function

Description

5 , 6

Motor thermistor input

This input allows a motor thermistor with a response value from 2.8 to 3.2K

, and a reset value from 0.75 to

1K

to control motor temperature.

When the motor thermistor is not used, a link must be used between terminals 5-6.

Communications
Terminal

Function

Description

TD, RD, SG

Tx, Rx, Gr data

RS232C, 3 wires, half duplex. Maximum cable length 3meters (10 feet).
Asynchronous data transmission, 9600 Bauds, 1 bit start, 8 bits data, 2 bits stop, no parity.

3-2