Appendix, 1. application diagrams, Basic diagram with linear ramp – GE Industrial Solutions ASTAT-CD Plus User Manual

Page 31

Advertising
background image

M

3 ~

L1

L2

L3

1 L1 3 L2 5 L3

A1 A2

B1 B2

A1 A2

B1 B2

57

57

57

6

8

12 11 14

23 24

33 34

1

2

Start

3

4

5

7

2 T1 4 T2 6 T3

9

Motor Thermistor

I3

I4

1r

2r

3r

Programmable Inputs

Programmable relay Outputs

TD RD SG

Control Voltage

110 / 120V AC

Control Voltage

220 / 240V AC

FLT (4)

DC1

DC1 (1)

Stop

Push-Button command (2)

6. Appendix

6-3

6-1. Application diagrams

Basic diagram with linear ramp

REMARKS:
(1)
The isolation contactor DC1, is not required to perform

operation to the motor.
Be aware however that DC1 provides galvanic isolation
from the incoming line increasing the safety.

(2) In this example, Start and Stop command is provided by

push-buttons. Permanent command is allowed as well,
wiring 1, 2 and 57 terminals as shown on page 3-3.

(3) The output relays allow for direct action on contactors

according to ratings specified in page 3-2 of this manual.

(4)

The ASTAT-CD Plus is provided with an electronic motor
overload protection, which should be adequate protec-
tion for most of the applications.
An external overload relay should be used if required
by local codes or to protect the motor against current
unbalance.

(5) Linear ramp provided by "Dxxx" function. A tacho

generator must be used as feedback. Details given
bellow.

Linear ramp function. Programming steps
1.
The linear ramp function may be enabled by setting

"Dxxx" to ON. In this case, linear ramp is independent of
the load.
This function needs the speed feedback provided by an
external tacho generator. Check section 4-6-2 for more
details.