5-3. Fuses, contactors and supply wiring

In

Total

Fuses

Fuses

Fuses

Control voltage

Contactor

Contactor

Conductor

losses

aM

FERRAZ type

BUSSMANN type

DC 1

DC 3

section

100% In

(F1)

(XX=according

(Typower Sicu 660V~)

Fuse

Consumpt.

(2)

Cat Number

A

W

A

mech. design)

Size

In

A

VA

mm

2

QC _ F DP

17

67

25

6,600 CP URC 14.51/40

00

40

1

18

CL02

CL02

4

QC _ G DP

21

78

32

6,6 URD 30 XX 0063

00

50

1

18

CL03

CL03

4

QC _ H DP

27

88

40

6,6 URD 30 XX 0080

00

80

1

18

CL04

CL03

6

QC _ I DP

38

116

63

6,6 URD 30 XX 0100

00

100

1

18

CL45

CL04

10

QC _ J DP

58

208

80

6,6 URD 30 XX 0125

00

125

2

55

CL07

CL45

16

QC _ K DP

75

277

100

6,6 URD 30 XX 0160

00

160

2

55

CL08

CL06

25

QC _ L DP

86

302

125

6,6 URD 30 XX 0160

00

200

2

55

CL09

CL06

35

QC _ M DP

126

389

200

6,6 URD 30 XX 0250

00

250

2

55

CK75

CL07

50

QC _ N DP

187

719

250

6,6 URD 30 XX 0315

00

315

2

78

CK08

CL10

95

QC _ Q DP

288

1097

400

6,6 URD 31 XX 0500

2

550

2

78

CK95

CK85

185

QC _ R DP

378

1286

500

6,6 URD 31 XX 0630

2

630

4

118

CK10

CK85

240

QC _ S DP

444

1374

630

6,6 URD 32 XX 0800

2

800

4

118

CK11

CK95

Bus bar (1)

QC _ T DP

570

2086

800

6,6 URD 33 XX 1000

3

1000

4

118

CK12

CK10

Bus bar (1)

QC _ U DP

732

2352

1000

6,6 URD 33 XX 1250

3

1250

4

248

CK12

CK10

Bus bar (1)

QC _ V DP

1020

3000

1250

6,6 URD 233 XX 2000

-

-

4

248

CK13

CK11

Bus bar (1)

QC _ X DP

1290

3839

2x800

6,6 URD 233 XX 2000

-

-

4

248

CK13

CK12

Bus bar (1)

5. Installation

In

Total

Fuses

Fuses

Fuses

Control voltage

Contactor

Contactor

Conductor

losses

aM

FERRAZ type

BUSSMANN type

DC 1

DC 3

section

100% In

(F1)

(XX=according

(Typower Sicu 660V~)

Fuse

Consumpt.

(2)

Cat Number

A

W

A

mech. design)

Size

In

A

VA

mm2

QC _ F DP

14

56

20

6,600 CP URC 14.51/40

00

40

1

18

CL01

CL01

4

QC _ G DP

17

65

25

6,6 URD 30 XX 0063

00

50

1

18

CL02

CL02

4

QC _ H DP

22

74

32

6,6 URD 30 XX 0080

00

80

1

18

CL03

CL03

4

QC _ I DP

32

99

63

6,6 URD 30 XX 0100

00

100

1

18

CL04

CL04

6

QC _ J DP

48

178

80

6,6 URD 30 XX 0125

00

125

2

55

CL06

CL04

10

QC _ K DP

63

236

80

6,6 URD 30 XX 0160

00

160

2

55

CL07

CL04

16

QC _ L DP

72

257

100

6,6 URD 30 XX 0160

00

200

2

55

CL08

CL06

25

QC _ M DP

105

325

160

6,6 URD 30 XX 0250

00

250

2

55

CL10

CL06

35

QC _ N DP

156

591

200

6,6 URD 30 XX 0315

00

315

2

78

CK75

CL07

70

QC _ Q DP

240

901

315

6,6 URD 31 XX 0500

2

550

2

78

CK85

CK75

120

QC _ R DP

315

1063

400

6,6 URD 31 XX 0630

2

630

4

118

CK95

CK85

185

QC _ S DP

370

1136

500

6,6 URD 32 XX 0800

2

800

4

118

CK10

CK85

240

QC _ T DP

475

1721

630

6,6 URD 33 XX 1000

3

1000

4

118

CK11

CK95

Bus bar (1)

QC _ U DP

610

1950

800

6,6 URD 33 XX 1250

3

1250

4

248

CK12

CK10

Bus bar (1)

QC _ V DP

850

2491

1000

6,6 URD 233 XX 2000

-

-

4

248

CK13

CK10

Bus bar (1)

QC _ X DP

1075

3168

1250

6,6 URD 233 XX 2000

-

-

4

248

CK13

CK12

Bus bar (1)

(1) As per IEC 947

(2) The 3 contacts of DC3 must be connected in parallel

IEC Class 10
Ratings

5-2

IEC Class 20
Ratings

Max. Fuse

Max. Circuit

Type

Type

Rating Class

Breaker

Non-

Cat Number

A50QS

1

A50P

2

RK5 & J

Size

Combination

Combination

<Remarks>

QC _ F DP

50A

-

30A

35A

25KA

5KA

QC _ G DP

60A

-

35A

40A

25KA

5KA

QC _ H DP

80A

-

40A

50A

25KA

5KA

QC _ I DP

100A

-

70A

80A

25KA

5KA

QC _ J DP

150A

-

100A

125A

25KA

10KA

QC _ K DP

200A

-

125A

150A

25KA

10KA

QC _ L DP

225A

-

150A

150A

25KA

10KA

QC _ M DP

350A

-

200A

250A

25KA

10KA

QC _ N DP

450A

-

350A

350A

65KA

25KA

QC _ Q DP

600A

-

500A

600A

65KA

25KA

QC _ R DP

2X500A in parallel

-

600A

700A

65KA

25KA

QC _ S DP

2x600A in parallel

-

600A

800A

65KA

25KA

QC _ T DP

-

2x1000A in parallel -

800A

65KA

30KA

*2

QC _ U DP

-

2x1200A in parallel -

1000A

65KA

30KA

*2

QC _ V DP

-

2x1600A in parallel -

1200A

65KA

65KA

Branch circuit protection, UL

Gould-Shawmut, semi-conductor fuses

Short-Circuit Rating Max @480V

NOTE: When ASTAT-CD Plus reduced voltage starters are used in conjunction with semi-conductor fuses, Type 2 Coordination to IEC 947-4 is attained. These
fuses are recommended for best overall short-circuit protection. The semiconductor fuse specified may provide branch circuit protection. Refer to local applicable
electrical codes.

(

1

) Suitable for use on a circuit capable of

delivering not more than 100KA RMS
symetrical amperes, for 208V, 240V and up to
480V maximum, when used with the semi-
conductor fuse for short-circuit protection. Listed
with Gould Shawmut Form 101, Type A5QS
or A50P.

(

2

)

Suitable for use on a circuit capable of
delivering not more than 65KA RMS symetrical
amperes, for 208V, 240V and up to 480V
maximum, when used with contactors (isolation
or by-pass) that are also rated for 65KA
withstand.