Programming, 7. application and basic settings, 8. saving parameters to e2prom – GE Industrial Solutions ASTAT-CD Plus User Manual

Page 24

Advertising
background image

4. Programming

4-9

Display

Parameter

Parameters

(1)

Factory

Default

4-7. Application and basic settings

Nominal motor current

N x x x

100

Current limit

L x x x

400

375

400

Initial torque

T x x x

025

030

035

020

020

Acceleration ramp time

a x x x

015

015

030

030

015

Deceleration ramp time

d x x x

020

040

Kick start time (2)

p x x x

000

100

Soft stop

S x x x

OFF

ON

Pump control

C x x x

OFF

ON

Pump curve starting

S T x x

02

02

Pump curve stopping

S P x x

02

02

Kick start

P x x x

OFF

ON

Overload trip curve(3)

o x x x

ooN2

ooN2

ooN2

ooC2

ooC1

ooC1

Service Factor(3)

f x x x

100

Compressor

Mill

Fan

Machine

Tool

Pump

Control

Settings (X X X)

Different applications will require different characteristics and settings for the ASTAT-CD Plus. The table below lists typical settings for
various applications.

Notes:

(1) = GBAS Block Parameters unless noted(2)(3)

(2) = Parameter “p” is disabled while “C” is ON.
(3) = GCAL Block Parameters

4-8. Saving parameters to E2PROM

Advance the display to K000 with
the C/V and up arrow button.

Change the parameter to K069 with
the up arrow button.

With K069 displayed, press the
enter button.

Display will show SET momentarily
and then display K ON.

Advance the display to WOFF with
the C/V and up arrow button.

Change parameter to W ON by using
the up arrow button.

With W ON displayed, press the
enter button.

Display the show SET momentarily
and then display WOFF.