Types and ratings, 2. ul ratings – GE Industrial Solutions ASTAT-CD Plus User Manual
Page 8
2. Types and Ratings
2-2
2-2. UL Ratings
(1)
Current
Max.
HEAVY DUTY
STANDARD DUTY
Degree of
Cat. No.
Weight
Cooled
rating
starting
200V
230V
460V
200V
230V
460V
protection
current
A
A
HP
HP
HP
HP
HP
HP
Kg.
Lbs.
14
63
3
3
7.5
3
3
7.5
IP-00
QC2FDP
4.3
9.48
Natural
17
77
3
3
10
3
3
10
IP-00
QC2GDP
4.3
9.48
Natural
22
99
5
7.5
15
5
7.5
15
IP-00
QC2HDP
4.6
10.14
Natural
34
153
7.5
7.5
20
10
10
25
IP-00
QC2IDP
4.6
10.14
Natural
48
216
10
15
30
15
15
30
IP-00
QC2JDP
12.5
27.56
By fan
63
284
15
20
40
20
20
40
IP-00
QC2KDP
12.5
27.56
By fan
72
324
20
20
40
20
25
50
IP-00
QC2LDP
17.0
37.48
By fan
105
473
30
30
60
30
30
75
IP-00
QC2MDP
17.0
37.48
By fan
156
702
40
50
100
50
60
125
IP-00
QC2NDP
45.0
99.20
By fan
240
1080
60
75
150
75
75
200
IP-00
QC2QDP
45.0
99.20
By fan
315
1418
75
100
200
100
125
250
IP-00
QC2RDP
55.0
121.25
By fan
370
1665
100
125
250
125
150
300
IP-00
QC2SDP
55.0
121.25
By fan
500
2250
150
150
350
150
200
400
IP-00
QC2TDP
80.0
176.36
By fan
630
2835
200
200
400
200
250
500
IP-00
QC2UDP
105.0 231.47
By fan
850
3825
250
300
600
300
350
700
IP-00
QC2VDP
120.0 264.54
By fan
Notes:
(1)
=
Ratings in Amps. given for ambient temperature up to 40
°
C and 1000m altitude.
Derate output current by 1.5% /
°
C above 40
°
C.
Derate output current by 1% / 100m above 1000m.