6. Appendix

24

1r

Programmable relay 11-12-14

R/W

22-30

See programmable
relays functions in page 3-6

25

2r

Programmable relay 23-24

R/W

20,22-30

26

3r

Programmable relay 33-34

R/W

21-30

27

OC

Overcurrent (%In)

R/W

0-50

0: OFF

28

oc

Overcurrent time (sec)

R/W

0-99

29

r

Reverse slow speed

R/W

0-3

0: OFF
1: ON
2: I3
3: I4

30

Y

Retry attempts

R/W

0-4

31

y

Retry time (sec)

R/W

1-99

32

UV

Undervoltage (%U)

R/W

0-50

0: OFF

33

uv

Undervoltage time (sec)

R/W

0-99

34

OV

Overvoltage (%U)

R/W

0-30

0: OFF

35

ov

Overvoltage time (sec)

R/W

0-99

36

UC

Undercurrent (%In)

R/W

0-99

0: OFF

37

uc

Undercurrent time (sec)

R/W

0-99

38

PF

Power factor (%)

R/-

00-99

39

U

Nominal voltage (volt)

R/W

100-500

40

V

Line voltage (volt)

R/-

41

w

Power (KW*10)

R/-

42

X

Local/remote control

0-3

0: OFF
1: ON
2: I3
3: I4

43

D

Linear ramp control

R/W

0-3

0: OFF
1: ON
2: I3
3: I4

44

J

Slow speed control

R/W

0-2

0: OFF
1: I3
2: I4

45

j

Slow speed type

R/W

0-1

0: HI
1: LO

46

2a

Secondary acceleration ramp time (sec)

R/W

1-99

47

2d

Secondary deceleration ramp time (sec)

R/W

1-99

48

A

Dual ramp selection

R/W

0-3

0: OFF
1: ON
2: I3
3: I4

49

UF

Unit frame

R/W

0-16

0: not defined
1 to 16: F to X frames

50

E

Elapsed time (hours)

R/-

51

—-

internal use

52

Q

Recall factory settings

-/W

1

53

2T

Secondary starting torque (%DOL torque)

R/W

10-90

54

m

Current calibration

R/-

55

—-

internal use

56

z

Bypass function

R/W

0-3

0: OFF
1: ON
2: I3
3: I4

57

—-

internal use

58

f

Service factor (%In)

R/W

100-130

59

t

Voltage calibration

R/-

000-600

60

RUN/STOP

RUN/STOP order

-/W

0: RUN
1: STOP

61

—-

internal use

62

—-

internal use

63

—-

internal use

64

—-

internal use