4. Programming

4-7

Programmable Basic Functions (follow from previous page)

By-pass selector

DC Brake selector

z x x x

B x x x

z O F F

B O F F

This function provides control of an external by-pass contactor,
significantly lowering heating losses and eliminating harmonics.
When the By-Pass function “z” is enabled, the programmable relay
output 2r is automatically assigned to this function, and must be used
to control the external by-pass contactor.

Enables or disables the DC brake function.
When the DC Brake function “B” is enabled, the programmable relay
output 3r is automatically assigned to this function.
PON, PI3 or PI4 settings enable the DC Brake function just before
starting the motor. This is usefull to stop a fan which is rotating in
reverse at the starting time.

OFF, ON, I3, I4

OFF, ON, I3, I4,

PON, PI3, PI4

Function

Display

Description

Default

Range

Unit

4-6. Advanced block parameters

-ADV-

Lock-out

E2PROM reading

Factory settings

Retry

Retry time

Undervoltage (1)

Undervoltage trip time

Overvoltage (1)

Overvoltage trip time

Undercurrent

Undercurrent trip time

Overcurrent

Overcurrent trip time

Dual ramp up
Dual ramp down
Dual starting torque

L K x x

R x x x

Q x x x

Y

x

y

x x

U V x x

u v x x

O V x x

o v x x

U C x x

u c x x

O C x x

o c x x

2 a x x
2 d x x
2 T x x

L K 0 2

R O F F

Q O F F

Y

0

y

1 0

U V 0 0

u v 2 0

O V 0 0

o v 2 0

U C 0 0

u c 2 0

O C 0 0

o c 2 0

2 a 1 5
2 d 2 0
2 T 2 0

Sets time between consecutive starts. Setting "0" disables
this function.

Loads the parameters from the E2PROM to the temporal
buffer.

Loads default factory settings to the temporal buffer.
Resave to E2PROM if default settings are desired.

Allows up to four tries of automatic restart after a fault.
Setting “0” disables this function.
Time between retries.

The unit trips if the line voltage decreases below the
percentage set. Setting “0” disables this protection.
NOTE: Perform voltage calibration procedure on page

4-5 before enabling this protection.

Delay trip time.

The unit trips if the line voltage increases above the per-
centage set. Setting “0” disables this protection.
NOTE: Perform voltage calibration procedure on page

4-5 before enabling this protection.

Delay trip time.

The unit trips if the current decreases below the percent-
age set. Setting “0” disables this protection.
NOTE: Perform current calibration procedure on page

4-5 before enabling this protection.

Delay trip time.

The unit trips if the current increases above the percent-
age set. Setting “0” disables this protection.
NOTE: Perform current calibration procedure on page

4-5 before enabling this protection.

Delay trip time.

These are a secondary set of ramp up, ramp down and
starting torque parameters, which take over the primary
"a", "d" and "T" when the programmable function “A” is
enabled.

00-45

ON, OFF

ON, OFF

0-4

01-99

00-50

00-99

00-30

00-99

00-99

00-99

00-50

00-99

01-99
01-99
10-90

min.

-

-

-

sec.

%

sec.

%

sec.

%

sec.

%

sec.

%
%
%

4-6-1. Advanced functions

Note:

(1) Monitors L1

Advertising