Function

Display

Description

Default

Range

4-6-2. Programmable advanced functions

Linear ramp

Slow speed

Speed changeover

Reverse

Dual motor selector

Remote control selector

Comunication protocol

Station number

D x x x

J x x x

j

x x

r

x x x

A x x x

X x x x

X P x x

s x x x

D O F F

J O F F

j

L O

r

O F F

A O F F

X O F F

X P 0 0

s 0 0 1

This function provides linear acceleration and deceleration ramps in
a wider range of load conditions using tachogenerator feedback.
A DC Tacho-Generator coupled to motor must be used to provide an
analog signal feedback of 0-5VDC to terminals 7 and 8.

This function enables slow speed operation
Maximum operation time 120sec.
LO: Low Speed, 7% of rated speed.
HI: High Speed, 14% of rated speed.
Reverse direction is allowed in "High slow speed" mode only.
It provides 20% of rated speed.

This function allows dual motor control settings of acceleration,
deceleration and starting torque, and is useful to start or stop a motor
in diferent load conditions.
When this function is enabled, the parameters 2a, 2d and 2T take
over the parameters a, d and T. It allows dual motor control settings.

Allows serial communication control by SG, TD and RD terminals.
Check Appendix section for more details
Sets serial communications protocol
0: ASCII 1: Future use
2: Future use

ASCII protocol allows a maximum of 90 stations only.

OFF, ON, I3, I4

OFF, I3, I4

LO, HI

OFF, ON, I3, I4

OFF, ON, I3, I4

OFF, ON, I3, I4

00-02

001-247

Function

Display

Description

Default

Range

4-6-3. Programmable relay output functions

Output relay 1r

Output relay 2r

Output relay 3r

1 r

x x

2 r

x x

3 r

x x

1 r

2 5

(RUN)

2 r

2 0

(EOR)

3 r

2 1

(DC Brake)

This is a programmable relay with one NO / NC dry contact to
ASTAT-CD Plus terminals 11-12-14.

This is a programmable relay with one NO dry contact to ASTAT-CD
Plus terminals 23-24.
This relay is automatically assigned to BY-Pass control if the function “z”
is ON. Any other assignment by the user is overwritten in this case.

This is a programmable relay with one NO dry contact to ASTAT-CD
Plus terminals 33-34.
This relay is automatically assigned to DC-Brake control if the
function “B” is ON. Any other assignment by the user is overwritten in
this case.

22-30

20, 22-30

21-30

The programmable relays can be set to the functions shown in the following table:

Function

EOR
DC Brake
FAULT
Undervoltage
Overvoltage
RUN
Slow Speed
Undercurrent
Overcurrent
Disabled
Future use

Remarks

Detects end of voltage ramp. -This function may only be assigned to relay 2r-
DC Brake control command -This function may only be assigned to relay 3r-
Detects unit Fault status. ON is normal status and switches OFF if a fault occurs
Detects Undervoltage according limit adjusted in function “UV”
Detects Overvoltage according limit adjusted in function “OV”
Detects unit RUN status
Detects slow speed status
Detects Undercurrent according limit adjusted in function “UC”
Detects Overcurrent limits as adjusted in function “OC”
Disables the relay function

Range

20
21
22
23
24
25
26
27
28
29
30

4. Programming