Appendix, 1. application diagrams, Basic diagram – GE Industrial Solutions ASTAT-CD Plus User Manual

Page 29: Basic diagram with by-pass control

Advertising
background image

A1 A2

B1 B2

57

57

57

6

8

12 11 14

23 24

33 34

1

2

Start /Stop

(Permanent Command)

3

4

5

7

9

57

57

1

2

Start Stop

(Command by push-buttons)

Prog

ra

mmab

le

Inputs

Motor Ther

mistor

Input

T

acho f

eedbac

k

Analog Input

0-10V

Analog Output

V

+

-

-

+

I3

I4

1r

2r

3r

Programmable Inputs

Programmable Relay Outputs

TD RD SG

Tx

M2

Bypass

Rx Gr

Serial Comm.

RS232C

A1 A2

B1 B2

Control Voltage

110 / 120V AC

Control Voltage

Control Voltage

220 / 240V AC

DC2

DC1

M

3 ~

L1

L2

L3

1 L1 3 L2 5 L3

2 T1 4 T2 6 T3

M

3 ~

L1

L2

L3

1 L1 3 L2 5 L3

A1 A2

B1 B2

A1 A2

B1 B2

57

57

57

6

8

12 11 14

23 24

33 34

1

2

Start

3

4

5

7

2 T1 4 T2 6 T3

9

Motor Thermistor

I3

I4

1r

2r

3r

Programmable Inputs

Programmable relay Outputs

TD RD SG

Control Voltage

110 / 120V AC

Control Voltage

220 / 240V AC

FLT (4)

DC1

DC1 (1)

Stop

Push-Button command (2)

6. Appendix

6-1

6-1. Application diagrams

Basic diagram

REMARKS:
(

1) The isolation contactor DC1, is not required to perform

operation to the motor.
Be aware however that DC1 provides galvanic
isolation from the incoming line increasing the safety.

(2) In this example, Start and Stop command is enabled

by push-buttons. Permanent command is allowed as
well, wiring 1, 2 and 57 terminals as shown on
page 3-3.

(3) The output relays allow for direct action on contactors

according to ratings specified on page 3-2 of this
manual.

(4) The ASTAT-CD Plus is provided with an electronic

motor overload protection, which should be adequate
protection for most of the applications.
An external overload should be used if required by
local codes or to protect the motor against current
unbalance.

Basic diagram with by-pass control

REMARKS:
(1)
The isolation contactor DC1, is not re-

quired to perform operation to the motor.
Be aware however that DC1 provides gal-
vanic isolation from the incoming line in-
creasing the safety.

(2) In this example, Start and Stop command

is enabled by permanent command. Push-
button control is allowed as well, wiring 1,
2 and 57 terminals as shown on page 3-3.

(3) The output relays allow for direct action on

contactors according to ratings specified
in page 3-2 of this manual.

(4) CAUTION:

In by-pass mode an external overload
relay must be used.

(5) By-pass control using function "zxxx" and

external contactor DC2. Details given bel-
low.

By-pass control. Programming steps
1.
The by-pass function may be enabled by

setting "zxxx" to ON. In this case the by-
pass is automatically done after starting.
An alternative, if "zxxx" is set to one of the
programmable inputs "I3" or "I4", the by-
pass may be controlled by one remote
signal (5). Check section 4-5-2 for more
details.

2. Once this function is enabled, the relay 2r

is automatically assigned to this function
(check section 4-6-3). This relay must be
used to control the by-pass contactor.

Advertising