3-5. Programmable Inputs and Outputs

Programmable inputs and functions

3. Technical Specifications

The ASTAT-CD Plus functions such as soft stop, kick start, etc., can be enabled (ON) or disabled (OFF) in their dedicated parameters by using the keypad.
Most of these functions can be enabled or disabled remotely as well, through the programmable inputs I3 or I4 (terminals 3-57 and 4-57).

Soft Stop

Pump Control

Kick Start

Override

By-pass

DC Brake

Linear Ramp

(Jog). Slow Speed

Reverse Jog

Dual Motor

Remote Control

S x x x
C x x x
P x x x
F x x x
z x x x
B x x x
D x x x
J x x x
r

x x x

A x x x
X x x x

_ O F F

_

O N

_

I

3

_

I

4

Function

Parameter

Set Value

The function is permanently disabled

The function is permanently enabled

The status of the function depends upon I3 input

The status of the function depends upon I4 input

NOTE: One programmable input may enable or

disable more than one function

<Remarks>

Programmable Relay Outputs

The ASTAT-CD Plus includes three programmable relays 1r, 2r and 3r (dry contacts). ASTAT-CD Plus terminals are 11-12-14, 23-24 and 33-34
These relays can be assigned to several functions, as shown below.

Relay 1r

Relay 2r

Relay 3r

20

21

22

23

24

25

26

27

28

29

30

EOR

Detects end of voltage ramp. -This function can only be assigned to relay 2r-

DC Brake

DC Brake command -This function can only be assigned to relay 3r-

Fault

Detects ASTAT-CD Plus fault status

Undervoltage

Detects limit set in parameter UVxx (1)

Overvoltage

Detects limit set in parameter OVxx (1)

RUN

Detects ASTAT-CD Plus run status

JOG

Detects Jog (slow speed) status

Undercurrent

Detects limit set in parameter UCxx

Overcurrent

Detects limit set in parameter OCxx

Disabled

Disables the relay function

Future use

Relay N#

Parameter

1 r

x x

1 r

x x

3 r

x x

Set Value

<Remarks>

3-6

More than one function can be enabled in the ASTAT-CD Plus, either by the keypad or through the programmable inputs I3 and I4, but there are some functions
which may not work as expected during stopping, such as when they are simultaneously enabled. When two or more of the below functions are simultaneously
enabled, the priority is defined in the following table:

DC Brake (B=ON)

a

b

c

Linear Ramp (S, D=ON)

a

a

a

Soft Stop (S=ON)

b

a

c

Pump Control (S, C=ON)

c

a

c

DC Brake (B=ON)

Linear Ramp (S, D=ON)

Soft Stop (S=ON)

Pump Control (S, C=ON)

a

The unit stops by Linear Ramp

b

The unit stops by DC brake after the Soft Stop is completed.

c

The unit stops by Pump Control

○○○○○○○○

○○○○○○○○

○○○○○○○○

Condition

Action

Note: (1) Monitors L1