Appendix – GE Industrial Solutions ASTAT-CD Plus User Manual

Page 34

Advertising
background image

Parameter

Parameter

Function

Read/Write

Range

Comments

number

name

(R/W)

0

Status

Soft starter status

R/-

0 - 14

0: ON
1: STOP
2: LOCK
3: Alarm (errors)
4: PULS
5: RAMP
6: FULL
7: SAVE
8: SOFT
9: DCBK
10: FULL (override)
11: Not used
12: INCH
13: TACH
14: PUMP

1

M

Motor current

R/-

% In or Amps depending on UF parameter

2

N

Nominal motor current (% In/Ir)

R/W

40-120

3

L

Current limit (% Im/In)

R/W

100-700

4

T

Starting torque (% DOL torque)

R/W

10-90

5

a

Acceleration ramp time (sec)

R/W

1-99

6

d

Deceleration ramp time (sec)

R/W

1-120

7

p

Kick start time (msec)

R/W

0-999

8

b

DC brake time (sec)

R/W

0-99

9

I

DC brake current (% In)

R/W

000-250

10

S

Soft stop control

R/W

0-3

0: OFF
1: ON
2: I3
3: I4

11

C

Pump control

R/W

0-3

0: OFF
1: ON
2: I3
3: I4

12

P

Kick start control

R/W

0-3

0: OFF
1: ON
2: I3
3: I4

13

F

Override

R/W

0-3

0: OFF
1: ON
2: I3
3: I4

14

B

DC brake control

R/W

0-6

0: OFF
1: ON
2: I3
3: I4
4: PON
5: PI3
6:PI4

15

LK

Lockout (min.)

R/W

0-45

16

o

Overload trip curve

R/W

0-5

0: OFF
1: N1
2: N2
3: N3
4: C1
5: C2

17

internal use

18

W

Write EEPROM

-/W

1

19

R

Read EEPROM

-/W

1

20

—-

internal use

21

v

Software version

R/-

xxx

vxxx

22

—-

internal use

23

—-

internal use

6. Appendix

6-2-3. List of parameters that can be controlled by the serial interface

6-6