Types and ratings, 3. astat, Cd plus, thermal characteristics – GE Industrial Solutions ASTAT-CD Plus User Manual
Page 9
2-3. ASTAT
®
-CD Plus, Thermal characteristics
The ASTAT-CD Plus allows the user to select motor protection according to IEC Class 10, 20 and NEMA 10, 20 or 30, selectable by "o" -overload- parameter
2. Types and Ratings
2-3
IEC Class 10
IEC Class 20
NEMA 10
NEMA 20
NEMA 30
Thermal memory:
If the control voltage is not removed, the unit has a cool down
characteristic. The time for cool down is 300 sec. after the overload trip.
If the control voltage is removed after tripping, you must wait at least 2
minutes before the unit can be restarted.
Operations per hour:
Using a cycle T, with starting time of t1, running time of T-2t1 at rated
current and OFF time of t1 sec. (minimum), the ASTAT-CD Plus allows
the following operations per hour.
Starting
Operations / Hour.
Operations / Hour
Current
Starting time t1= 10sec.
Starting time t1=20 sec.
Sec.
Sec.
Sec.
Sec.
Sec.
2 Ir
180
90
3 Ir
160
60
4 Ir
30
10
COLD
HOT
COLD
HOT
HOT
COLD
HOT
COLD
HOT
COLD
Multiples of motor FLA rating I
n
Multiples of motor FLA rating I
n
Multiples of motor FLA rating I
n
Multiples of motor FLA rating I
n
Multiples of motor FLA rating I
n