Types and ratings, 3. astat, Cd plus, thermal characteristics – GE Industrial Solutions ASTAT-CD Plus User Manual

Page 9

Advertising
background image

2-3. ASTAT

®

-CD Plus, Thermal characteristics

The ASTAT-CD Plus allows the user to select motor protection according to IEC Class 10, 20 and NEMA 10, 20 or 30, selectable by "o" -overload- parameter

2. Types and Ratings

2-3

IEC Class 10

IEC Class 20

NEMA 10

NEMA 20

NEMA 30

Thermal memory:
If the control voltage is not removed, the unit has a cool down
characteristic. The time for cool down is 300 sec. after the overload trip.
If the control voltage is removed after tripping, you must wait at least 2
minutes before the unit can be restarted.

Operations per hour:
Using a cycle T, with starting time of t1, running time of T-2t1 at rated
current and OFF time of t1 sec. (minimum), the ASTAT-CD Plus allows
the following operations per hour.

Starting

Operations / Hour.

Operations / Hour

Current

Starting time t1= 10sec.

Starting time t1=20 sec.

Sec.

Sec.

Sec.

Sec.

Sec.

2 Ir

180

90

3 Ir

160

60

4 Ir

30

10

COLD

HOT

COLD

HOT

HOT

COLD

HOT

COLD

HOT

COLD

Multiples of motor FLA rating I

n

Multiples of motor FLA rating I

n

Multiples of motor FLA rating I

n

Multiples of motor FLA rating I

n

Multiples of motor FLA rating I

n