background image

HEAVY DUTY (2)

LIGHT DUTY

Degree of

Cat. No.

Weight

Cooled

Current

220V /

380V /

440V

480V /

Current

220V /

380V /

440V

480V /

protection

rating

240V

415V

500V

rating (3)

240V

415V

500V

A

kW(4)

kW(4)

kW(4)

kW(4)

A

kW(5)

kW(5)

kW(5)

kW(5)

Kg.

Lbs.

14

3

5.5

7.5

-

17

4

7.5

7.5

-

IP-00

QC1FDP

4.3

9.48

Natural

3

5.5

7.5

7.5

4

7.5

7.5

11

IP-00

QC2FDP

4.3

9.48

Natural

17

4

7.5

7.5

-

21

5.5

11

11

-

IP-00

QC1GDP

4.3

9.48

Natural

4

7.5

7.5

11

5.5

11

11

13

IP-00

QC2GDP

4.3

9.48

Natural

22

5.5

11

11

-

27

7.5

13

15

-

IP-00

QC1HDP

4.6

10.14

Natural

5.5

11

11

15

7.5

13

15

15

IP-00

QC2HDP

4.6

10.14

Natural

32

7.5

15

18.5

-

38

10

18.5

22

-

IP-00

QC1IDP

4.6

10.14

Natural

7.5

15

18.5

22

10

18.5

22

25

IP-00

QC2IDP

4.6

10.14

Natural

48

13

22

22

-

58

15

25

30

-

IP-00

QC1JDP

12.5

27.56

By fan

13

22

22

30

15

25

30

37

IP-00

QC2JDP

12.5

27.56

By fan

63

15

30

37

-

75

22

37

45

-

IP-00

QC1KDP

12.5

27.56

By fan

15

30

37

37

22

37

45

45

IP-00

QC2KDP

12.5

27.56

By fan

72

20

37

37

-

86

25

45

50

-

IP-00

QC1LDP

17.0

37.48

By fan

20

37

37

45

25

45

50

50

IP-00

QC2LDP

17.0

37.48

By fan

105

30

55

55

-

126

37

63

75

-

IP-00

QC1MDP

17.0

37.48

By fan

30

55

55

75

37

63

75

80

IP-00

QC2MDP

17.0

37.48

By fan

156

40

75

90

-

187

55

90

110

-

IP-00

QC1NDP

45.0

99.20

By fan

40

75

90

110

55

90

110

132

IP-00

QC2NDP

45.0

99.20

By fan

240

63

110

132

-

288

80

150

165

-

IP-00

QC1QDP

45.0

99.20

By fan

63

110

132

160

80

150

165

200

IP-00

QC2QDP

45.0

99.20

By fan

315

90

160

200

-

378

110

200

220

-

IP-00

QC1RDP

55.0

121.3

By fan

90

160

200

220

110

200

220

250

IP-00

QC2RDP

55.0

121.3

By fan

370

110

200

220

-

444

132

220

250

-

IP-00

QC1SDP

55.0

121.3

By fan

110

200

220

250

132

220

250

315

IP-00

QC2SDP

55.0

121.3

By fan

475

150

250

250

-

570

160

300

355

-

IP-00

QC1TDP

80.0

176.4

By fan

150

250

250

335

160

300

355

400

IP-00

QC2TDP

80.0

176.4

By fan

610

200

315

400

-

732

220

400

450

-

IP-00

QC1UDP

105.0 231.5

By fan

200

315

400

400

220

400

450

500

IP-00

QC2UDP

105.0 231.5

By fan

850

250

450

530

-

1020

300

560

600

-

IP-00

QC1VDP

120.0 264.5

By fan

250

450

530

600

300

560

600

750

IP-00

QC2VDP

120.0 264.5

By fan

1075

355

600

670

-

1290

395

715

750

-

IP-00

QC1XDP

150.0 330.7

By fan

355

600

670

750

395

715

750

850

IP-00

QC2XDP

150.0 330.7

By fan

2. Types and Ratings

2-1

2-1. IEC Ratings (1)

Notes:

(1)

=

Ratings in Amps. given for ambient temperature up to 40

°

C and 1000m altitude.

Derate output current by 1.5% /

°

C above 40

°

C.

Derate output current by 1% / 100m above 1000m.

(2)

=

Heavy duty ratings, IEC Class 10 and 20 protections allowed.

(3)

=

Light duty ratings, only IEC Class 10 protection allowed.

(4)

=

Maximum recommended Motor Power for IEC Class 20 protection. Set ASTAT-CD Plus's parameters "N" and "o" accordingly.

(5)

=

Maximum recommended Motor Power for IEC Class 10 protection. Set ASTAT-CD Plus's parameters "N" and "o" accordingly.

Advertising