3.4 PLACE OF INSTALLATION

The UPS should be installed in a restricted area where only qualified personnel should be admitted.

The place of installation should be clean, dust-free, and provided with proper ventilation or air-
conditioning
.

Verify for sufficient floor load capacity (see Section 3.1.1).

We strongly advice that the ambient temperature should not exceed 68° - 77°F / 20° - 25°C (max. 104°F
/ 40°C). See Section 3.5.

Positioning of the UPS LP33 Series 80 & 100

LPS33U_0

80-100_UP

S dispositio

n_GE_01

Min.

41" / 1040mm

Min. 16" / 400mm

Fig. 3.4-1 LP33 Series 80 & 100 positioning

The rear panel of the UPS may be mounted
flush to a wall or other structure.


Clearance around the front of the unit
should be sufficient to enable free passage
of personnel with the doors fully open, and
to allow sufficient airflow to the door vents.


To guarantee proper cooling air exhaust, the
recommended minimum clearance between

ceiling and top of the UPS is 16” (400mm).


In case of additional cabinets (external
batteries), this must be placed beside the left
side of the UPS cabinet.


A single-phase power outlet (208 Vac)
should be provided near the UPS for
connection of power tools, test equipment
or connectivity devices.
This outlet must be grounded.

The LP33 Series 80 & 100 UPS can radiate radio frequency energy.
Although some RFI (Radio Frequency Interference) filtering is inherent to the UPS there is no guarantee
that the UPS will not influence sensitive devices such as cameras and monitors that are positioned close
by.
If interference is expected, the UPS should be moved away from the sensitive equipment.

NOTE !

Operating temperature is very important for valve regulated battery (maintenance
free).
Operation at temperatures higher than 68°F (20°C) will reduce life expectancy.
Respect the prescription of the battery supplier and other local standards.
The installation and cabling of the battery must be must be performed by
QUALIFIED SERVICE PERSON
..