Installation Guide LP33 Series 80 & 100 UL S1

EPO (Emergency Power Off)


An external Emergency switch (NC - Normally Closed voltage-free contact) can be connected on

terminals X2 / 1, 2 or connector J2 / 12, 25 of the Customer Interface (see Fig. 4.4-1 / X2 & J2).

7

89

10

11

22

21

20

19

18
7

J2

X1

2
1

JP3
X2

Fig. 4.4-2 PCB Customer Interface

LPS33U_0

80-100_U

PS+X7_01

Q2

I ON

0 O

FF

I ON

0 O

FF

F11-12-13

1

2

JP5

X7

P1 - Control board

Fig. 4.4-3 PCB P1 – Control board

NOTE !

To enable this function, remove Jumper JP3 on the Customer Interface and the
cable on the terminal X2 / 1, 2
(see Fig. 4.4-2).
Verify if the cable on the terminal X7 / 1, 2 and Jumper JP5 on the P1 – Control
board
are OFF (see Fig. 4.4-3).

In a parallel system a separate NC (Normally Closed) contact must be connected
individually to each unit
.


When activated, this switch causes the immediate shutdown of booster, battery-charger, inverter; and
the contactors K4, K6 and K7.

NOTE !

This procedure could imply a Load shutdown.


When the EPO has been activated, the system must be restored as follows:

Press the push-button EPO (contact on X7 / 1, 2 is closed again).

Press the key O (Inverter OFF – see Section 6.2 of Operational Manual) on the control panel.

Press the key I (Inverter ON – see Section 6.2 Operational Manual) on the control panel.

In case of a Parallel System press the key “O” (Inverter OFF) on the control panel of
each unit connected on the parallel bus and having its output switch Q1 closed.