5 epo with battery disconnection (option), Male, Female – GE Industrial Solutions LP33 Series 80 & 100 Installation Guide User Manual

Page 45

Advertising
background image

Modifications reserved

Page 45/47

OPM_LPS_3UI_80K_M10_1US_V010.doc

Installation Guide LP33 Series 80 & 100 UL S1

5 EPO WITH BATTERY DISCONNECTION (OPTION)

WARNING !

Connections described in this chapter shall be done only by a GE SERVICE ENGINEER.


1

3

6

2

5

4

XA

LPS33U_080-100_UPS+EPO XA

_01

Q2

Q1

Q2

Q1

UPS cabinet

Battery cabinet

26"/650mm

Battery cabinet

48"/1215mm

XB -

Male

XB -

Female

Fig. 5-1 Terminals XA and connector XB – EPO with Battery disconnection


An external Emergency switch (NC - Normally Closed voltage-free contact) can be connected on

terminals XA / 3, 4 (see Fig. 5-1).
When activated, this switch causes the immediate shutdown of Booster, Battery-charger, Inverter;
Contactors K4, K6, K7 and the Battery Breaker FTM3.