5 EPO WITH BATTERY DISCONNECTION (OPTION)
WARNING !
Connections described in this chapter shall be done only by a GE SERVICE ENGINEER.
1
3
6
2
5
4
XA
LPS33U_080-100_UPS+EPO XA
_01
Q2
Q1
Q2
Q1
UPS cabinet
Battery cabinet
26"/650mm
Battery cabinet
48"/1215mm
XB -
Male
XB -
Female
Fig. 5-1 Terminals XA and connector XB – EPO with Battery disconnection
An external Emergency switch (NC - Normally Closed voltage-free contact) can be connected on
terminals XA / 3, 4 (see Fig. 5-1).
When activated, this switch causes the immediate shutdown of Booster, Battery-charger, Inverter;
Contactors K4, K6, K7 and the Battery Breaker FTM3.